Accessories for Control Panels and Keypads | Expansion Modules | 75
DS7457i Series Single Zone
Input Modules
Features
▶
Power-limited and supervised input zones
▶
Compact enough to fit within most back boxes and
enclosures
▶
Address settings through DIP switches
The DS7457i Series Single Zone Input Modules includes the
DS7457i and the DS7457iF. Each model has a supervised
input zone for connecting normally-open (NO) or normally-
closed (NC) contacts. The DS7457i Series supervises the
contacts using 47 kΩ end-of-line(EOL) resistors. Each
model operates with compatible multiplex expansion
modules and occupies one multiplex zone address on the
system. The DS7457i is designed for intrusion applications
while the DS7457iF is designed for fire applications.
Certifications and Approvals
Region Certification
Europe CE DS7457iF: 89/336/EEC, EN55022:
1998, EN50130-4: 1995, EN60950:
2000, EN61000-3-2, EN61000-3-3,
EN61000-4-2, EN61000-4-3,
EN61000-4-4, EN61000-4-5,
EN61000-4-6, EN61000-4-11
USA UL Both models: AMCX: Central Station Alarm
Units (UL1610, UL1635), AOTX: Local
Alarm Units (UL464, UL609), APAW:
Police Station Alarm Units (UL365,
UL464)
DS7457iF only: NBSX: Household Burglar
Alarm System Units (UL1023), UOXX:
Control Unit Accessories, System (UL864,
9th edition), UTOU: Control Units and
Accessories - Household System Type
(UL985)
CSFM DS7457iF only: 7165-1615: 113,
7165-1615: 199, 7170-1615: 144, and
7170-1615: 145 July 2008
Installation/Configuration Notes
Compatibility Information
Control Panels D9412GV2, D7412GV2, and D7212GV2 Con-
trol Panel
D9412G , D7412G, and D7212G Control Panels
D9412, D7412, and D7212 Control Panels
DS7400Xi Control Panel
Multiplex Modules D8125MUX Multiplex Bus Interface
DS7430 Multiplex Expansion Module
DS7436 Multiplex Expansion Module
The DS7457i Series Modules require a multiplex expansion
module to connect to the control panels.
Wiring Considerations
Maximum Impedance: 4.05 Ω at +20°C (+68°F) nominal
Distance (approximate) Size
76 m 0.65 mm
193 m 1.02 mm
250 ft 22 AWG
600 ft 18 AWG
Refer to the intended control panel’s installation guide for
multiplex wiring requirements.
The recommended wiring to the control panel is quad (four-
wire) cable. Do not use shielded or twisted pair cable.
Note If used in fire applications, 18 AWG wire is
required.
www.boschsecurity.com Bosch Security Systems B.V.
2