Bosch Appliances 8-Dec Home Security System User Manual


 
422 | Conettix - Information Transport Solutions | Conettix - AT2000/ATE
Operation using the primary multiplex connection S2M
is not possible.
The AT 2000 TSN ISDN communicator for danger alarms
must be connected to the S
0
bus as the first device.
With this connection, it is possible for the
AT 2000 TSN ISDN to send a message even in the event
of tampering or damage to the bus wiring.
ISDN PTP
The "constant monitoring" layer 1 feature is present by
default for system access.
The max. cable length from network termination NT via
the UAE 8/8 box to the TK system or to the end unit is
1000 m.
ISDN PMP
The "constant monitoring" layer 1 feature is also
required with a multi-system connection.
The max. cable length between network termination
and TK system or end unit is 150 m.
GSM transmission
The GSM network can also be used alone for a message
transmission (without ISDN).
For application according to VdS, only backup path
transmission from D1 to D1 or D2 to D2 is permissible.
Antenna planning
The antenna selection depends on the measured field
strength. The antenna and the cable must be selected
so that the measured attenuation on the AT 2000 does
not exceed -87 dB.
If the antenna is placed near an automatic fire or
intrusion detector, the distance of the antenna to the
detector must be at least 1 m.
We generally recommend the use of a radiator (rod
antenna for exterior and interior areas). If the reception
level implemented with a radiator is insufficient, beam
antennas (planar or exterior antennas for exterior and
interior areas) should be used.
With the installation of antennas outdoors, the relevant
DIN VDE provisions, especially DIN VDE 0845 part 1 and
VdS 2311 appendix F (protection against lightning)
must be adhered to! The ground connection isolator
and the lightning protection set (optional) are designed
for this.
Make measurements precisely where the antenna will
be mounted. The measurement results must remain
stable for a period of 10 minutes.
Antenna Gain Cable attenua-
tion
Comments
Magnet foot
antenna
0 dBi
(Entire system)
2.6 m fixed cable
with FME connec-
tor, female
Rod antenna 3.5 dBi
(Value without ca-
ble)
0.3 dB/m With 20 m fixed
cable, with FME
connector, fe-
male
Planar antenna 8 dBi According to ca-
ble type
Type of connec-
tion N-connector
Exterior antenna 10 dBi According to ca-
ble type
Connection type:
7/16 connector
Antenna cable
Cable type Cable
attenuation
Cable Ø Comments
Standard cable 0.3 dB/m Approx. 5 mm Low loss cable
Aircom Plus 0.15 dB/m 10.8 mm SOHA
If necessary, the pre-configured cables must be
shortened in order to avoid unnecessary attenuation.
The Aircom Plus cable must be used if the low-
attenuation standard cable achieves no level better
than -87 dBm.
Applications must strictly adhere to the bending radius
of at least 55 mm.
Product ID
4.998.066.838 Aircom Plus cable (SOHA)
4.998.066.839 Expansion module connector for the
Aircom Plus cable (SOHA)
Fire detection technology
Interface according to VDE 0833 part 2 can be provided
optionally.
Parts Included
Type Qty. Component
AT 2000 TSN ISDN 1 AT 2000 installation module with housing,
power supply unit and GSM module
Technical Specifications
Housing version
Current consumption
Standby current
Approx. 125 mA
ISDN transmission
Approx. 127 mA
GSM transmission
Approx. 255 mA
Additional current per activat-
ed relay
Approx. 12 mA
Terminal resistance of the
primary line
10 kilohm ± 1%
Activation time > 200 ms
Load on switch contacts
Max. output
30 W/60 VA (Ohm resistive load)
Max. voltage
50 V
ambient temperature -0 °C to +50 °C
Environmental class II
Protection category IP 40
Housing
Dimensions (H x W x D)
366 x 258 x 103 mm
Color
Light gray
Weight without/with battery
4.0/8.0 kg
Bosch Security Systems B.V. www.boschsecurity.com
7