Bosch Appliances 8-Dec Home Security System User Manual


 
402 | Conettix - Information Transport Solutions | Conettix - Receiver/Gateway Accessories
Conettix D6680 Ethernet
Network Adapter
Features
Two channel adapter
Network interface
Serial interface
The Conettix D6680 Ethernet Network Adapter is a two-
channel network adapter. The D6680 connects the Conettix
D6600 Communications Receiver/Gateway RS-232 Data
Port to an Ethernet LAN/WAN. One adapter is required for
each D6600 serial port with a direct connection to a data
network (LAN/WAN).
Certifications and Approvals
Install the Conettix D6600 Communications Receiver/
Gateway in accordance with NFPA 70, NFPA 72 and the local
Authority Having Jurisdiction (AHJ). The Conettix D6680
Ethernet Network Adapter is suitable for Central Station
Protective Signaling when it is installed and used in
compliance with NFPA 72 and ANSI/NFPA 70. Installation
limits for Digital Alarm Communicator Receivers (DACR) are
under the jurisdiction of the user’s local authority.
For UL Listed Fire Installations, equipment between
Ethernet Interface Modules and the D6680 is required to be
UL Listed Information Technology Equipment.
Region Certification
USA UL AMCX: Central Station Alarm Units
(UL1610, UL1635), UOXX: Control Unit
Accessories, System (UL864, 9th edition)
FM
CSFM 7300-1615: 179 July 2008
Installation/Configuration Notes
Compatibility Information
Receivers: Conettix D6600 Communications Receiver/Gate-
way
Location and Enclosures
The D6680 must be installed in the same room as the D6600
and within 15.2 m (50 ft) of the D6600. Required for UL
Central Station Protective Signaling, the D6680 must be
mounted in a separate enclosure such as the AE1 (gray) or
the AE2 (red).
Parts Included
Quantity Component
1 Serial cable
Technical Specifications
Electrical
Power Requirements: 9 VDC to 30 VDC, or 9 VAC to 25 VAC
External adapter included.
Power Consumption: 3 W
AC Current Required: UPS Standby Current:35 mA
Power Input: AC nominal operating range 120 VAC or
240 VAC
AC maximum operating range 100 VAC to
240 VAC ~ 50 Hz /60 Hz
0.2 A maximum
Standby Power: An Uninterrupted Power Supply is required for
use with the D6680, when used for UL FIRE
Protective
Signaling Systems. A 60 hour minimum UPS
standby power supply is required for UL Cer-
tification.
Mechanical
Unit Dimensions: 16.5 cm x 11.3 cm x 36 mm (6.5 in. x 4.46 in.
x 1.39 in.)
Enclosure Dimensions: 31.8 cm x 36.8 cm x 76 mm (12.5 in. x 14.5
in. x 3 in.)
The enclosure is manufactured from 1.0 mm
(20 Gauge), cold-rolled steel. A keyed lock is
included.
Weight: 0.48 kg (1.1 lb)
Protocols Supported: ARP, UDP, TCP, Telnet, ICMP, SNMP, DHCP,
TFTP, HTTP, BootP and ECHO
Serial Connectors: DB25: RS-232/RS-322/RS-485 serial port
with DCE configuration
DB9: RS232 serial port with DTE
configuration
Network Connectors: 10BASE-T or 10BASE-FL
LAN/WAN: RJ-45 Modular Jack (Ethernet)
Ethernet Cable: Category 3 or better unshielded twisted pair.
Maximum length 100 m (328 ft).
RS-232 Cable: Maximum length 15 m (50 ft).
Bosch Security Systems B.V. www.boschsecurity.com
7