342 | LSN Peripherals | LSN Smoke
Planning
Monitoring area
FAP-OTC 420,
FAP‑OT 420, FAP‑O 420
(KKW)
Max. 120 m
2
(Heed local guidelines!)
FAH-T 420 (KKW)
Max. 40 m
2
(Heed local guidelines!)
Maximum installation height 16 m (Heed local guidelines!)
FAP‑OTC 420,
FAP‑OT 420, FAP‑O 420
(KKW)
Max. 16 m (Heed local guidelines!)
FAH-T 420 (KKW)
Max. 7.5 m (Heed local guidelines!)
Further characteristics
Response sensitivity
Optical part
In accordance with EN 54 T7 (program-
mable)
Thermal maximum part
> 54 °C / >69 °C
Thermal differential part
A1R / A2R / BR, in line with prEN 54‑5
(programmable)
Gas sensor
In ppm range
Individual display LED red
Color code
FAP-OTC 420
Yellow loop
FAP-OT 420
Black loop
FAP-O 420 (KKW)
No marking
FAH-T 420 (KKW)
Red loop
Ordering Information
FAP‑OTC 420 Multisensor Detector Optical/
Thermal/Chemical
FAP-OTC 420
FAP‑OT 420 Multisensor Detector Optical/
Thermal
FAP-OT 420
FAP‑O 420 Optical Smoke Detector FAP-O 420
FAH‑T 420 Heat Detector
thermal differential/thermal maximum
FAH-T 420
FAP-OT 420 KKW multisensor detector
optical/thermal
FAP-OT420-KKW
FAP‑O 420 KKW Optical Smoke Detector
for use in areas with increased radioactive ra-
diation
FAP-O420-KKW
FAH‑T 420 KKW Heat Detector
thermal differential/thermal maximum, for use
in areas with increased radioactive radiation
FAH-T420-KKW
Accessories
MS 400 Detector Base
for surface-mounted and flush-mounted cable
feed
MS 400
MSF 400 Detector Base with Damp Room
Seal
for surface-mounted and flush-mounted cable
feed
MSF 400
MSC 420 Additional Base with Damp Room
Seal
for surface-mounted cable feed
MSC 420
Ordering Information
FAA‑MSR 420 Detector Base with Relay FAA-MSR 420
FAA‑MS 420‑R‑SP Detector Base with Relay
and Spring
for use in Great Britain
FAA-MS 420-R-SP
MS 420 LSN Detector Base with Spring
for use in Great Britain
MS 420
SSK 400 Protective Dust Cover
(packing unit = 10 units)
SSK 400
TP4 400 Support Plate for Detector
Identification
(packing unit = 50 units)
TP4 400
TP8 400 Support Plate for Detector
Identification
(packing unit = 50 units)
TP8 400
SK 400 Protective Basket SK 400
MH 400 Detector Heating Element MH 400
MK 400 Detector Console
Console for DIBt compliant mounting of detec-
tors above doors etc., including detector base
MK 400
Mounting Bracket for Fire Detectors on
False Floor Stilts
FMX-DET-MB
MPA External Detector Alarm Display
according to DIN 14623
MPA
FAA‑420‑RI Remote Indicator FAA-420-RI
Bosch Security Systems B.V. www.boschsecurity.com