Bosch Appliances 8-Dec Home Security System User Manual


 
36 | Control Panels, Control Centers, and Keypads | DS7080i
Program Memory
The control panel retains all program memory and the arm-
disarm state during a power failure. When power restores,
alarms are delayed to prevent false alarms from detectors
that can take several minutes to become operational. None
of the system programming or user codes are lost.
Flexible Digital Communication
The communicator works with most alarm receivers used
today. It supports 3/1, 4/1, 4/2, SIA, Contact ID, High Speed
4/9, BFSK digital communicator formats, and a pager
format. The pager format allows the control panel to dial a
digital pager service and leave a numeric message
representing the account number and event code.
Keypad Support
The DS7443S LED Keypad has one LED per zone (LEDs
1 to 6 for main board zones) and four system status
LEDs that indicate conditions such as armed, fire alarm,
and trouble.
The DS7445i or DS7445V2 Light-emitting Diode (LED)
Keypads have one LED per zone (LEDs 1 to 8 for main
board zones and LEDs 9 to 16 for expansion zones) and
eight system status LEDs that indicate conditions such
as armed, fire alarm, and trouble.
The DS7447E or DS7447V2 Alphanumeric Keypads have
two lines of custom-programmable display. You can
program 16 characters of custom text for zone and
partition descriptions. The user can adjust the sounder
volume and backlight intensity using easy two-button
commands. The DS7447E or DS7447V2 Keypad is
required for system programming.
Note LED and LCD keypads can be mixed in the
same system. Up to four keypads can be used,
but no more than two keypads on any 300 m
run.
Optional Eight-relay Output Module
The DS7488 module has eight Form C relays with fixed
functions such as alarm output, system ready, and panic.
Optional Solid-state Output Module
The DS7489 module has eight current-sink outputs, with
fixed functions, to operate devices such as LEDs and
sounders. Total current sink is 750 mA for all eight outputs.
Smoke Detector Alarm Verification
Program the DS7080iP-32 Control Panels to perform an
automatic reset on the smoke detectors if an alarm occurs.
If a second alarm occurs within the verification window, an
immediate fire alarm results. Fast response to a fire is
maintained while potential false alarms are reduced.
Three Telephone Numbers
The system supports two 20-digit telephone numbers with
a three- or four-digit account code. Configure each of the
two phone number's communication format and choice of
pulse or tone dialing. The third phone number is reserved
for remote programming.
Two Independent Entry Delays
Program zones to select one of two entry delay times. You
can select a longer entry delay time for zones that are
located a long distance from the keypad.
Certifications and Approvals
Region Certification
Europe CE 1999/5/EC, EN60950 Dec. 1992 (2nd
edition) +A1 (1992) +A2 (1993),
EN50081-1 (1992), EN50081-2 (1992)/
61000-4 series
Belgium INCERT B-509-0003/a Jan 2004
USA UL AMCX: Central Station Alarm Units
(UL1610, UL1635), AOTX: Local Alarm
Units (UL464, UL609), APAW: Police
Station Alarm Units (UL365, UL464),
APOU: Proprietary Alarm Units (UL1076),
NBSX: Household Burglar Alarm System
Units (UL1023)
USA FCC
Installation/Configuration Notes
Compatible Products
The following products are compatible with the
DS7080iP-32 Control Panels:
Keypads and An-
nunciators
DS7443S LED Keypad
DS7445i LED Keypad
DS7445V2 LED Keypad
DS7447E LCD Keypad
DS7447V2 LCD Keypad
Modules C900 Dialer Capture Module
C900TTL-E Dialer Capture Module
DS7480 Bell Supervision Module
DS7481 Single Phone Line Monitor
DS7488 Octal Relay Module
DS7489 Solid-state Output Module
Technical Specifications
Communicator
Phone Numbers: 2 phone numbers are available for report-
ing. A third number is available for remote
programming.
Report Formats: Full single, double and backup reporting
Communication Formats: SIA, 3/1 Ext, 4/1, 4/2, Contact ID, High
Speed 4/9, BFSK, and pager format
Ringer Equivalence: 0.1 B
Enclosure
Material: 1.0 mm, cold-rolled steel
Dimensions: 32 cm x 37 cm x 7.6 cm
Environmental Considerations
Relative Humidity: 5% to 85% at +30°C non-condensing
Temperature (Operating): 0°C to +49°C
Bosch Security Systems B.V. www.boschsecurity.com
1