Control Panels, Control Centers, and Keypads | UEZ 2000 | 61
SRT system parameters
Signaling devices 32 per system, max. 99 in the cluster
Transmission equipment 48 in the cluster
Auto dialer 1 per system
Printer 1 per system
Timer channels 9 per system
BE 1000 operating unit 4 per system
Priority control panel 2 per system
Alarm counter 2 per system
Event database 1 per system
Internal programs 14 in cluster
User ID Up to 255 in cluster
Monitoring texts Up to 20 in cluster
Alarm texts Up to 40 in cluster
System short texts Up to 300 in cluster
Detector short texts (location) 2032 in cluster
Hold-up camera 6 per system
Partitions 32 in cluster
Creating loop and stub lines
Basic version with 1 x LVM 100
(4 loops or 8 stubs or any preferred combination of the two)
Extension with second LVM 100 (only with UEZ 2000 LSN)
(Additional 4 loops or 8 stubs or any preferred combination
of the two)
1 Loop connection
2 Stub connection
3 LSN elements
NVU parameters: 2 loops or 4 stubs, up to 1000 m in cable
length, up to 100 mA current consumption, up to 127 LSN
elements
Quantity structure for the SRT system cluster with UEZ
2000 LSN
Maximum number of detectors
Number of
systems
1 2 3 4 5 6
508 1016 1524 2032 2032 2032
Maximum number of detector zones
Number of
systems
1 2 3 4 5 6
127 256 381 508 508 508
Module quantity structure in UEZ 2000 LSN emergency
call SRT
Quantity structure
Loops
Optocou-
pler
Fiber op-
tics or mo-
dem
UEZ 2000 LVM 100 SEMO SM20* SM24*
4 1
8 1 1
12 2 1 2 4 4
16 2 2 2 4 4
20 3 2 3 6 6
24 3 3 3 6 6
28 4 3 4 8 8
32 4 4 4 8 8
36 5 4 5 10 10
40 5 5 5 10 10
44 6 5 6 12 12
48 6 6 6 12 12
* Either a modem or a fiber optics converter is required in addition
to the SM 24
Note The limit values for each NVU or LVM 100 must
be observed.
Note For mixed configurations, the number of SM20
and SM24 modules required changes
(increases or decreases).