Bosch Appliances 8-Dec Home Security System User Manual


 
Conettix - Information Transport Solutions | Conettix - AT2000/ATE | 417
AT 2000 Analog Transmis-
sion System
Features
7 parallel inputs, 2 outputs (12 in/12 out optional)
Programmable with PC software (WPAT)
Tone and pulse dialing methods
Tamper and blockade release
The AT 2000 Analog and AFS auto dialers and
communicators handle the analog transmission of danger
alarms, technical alarms/statuses via telecommunication
networks.
Functions
Network ac-
cess
Transmission
procedure
Transmission
protocol
Receiver
Analog net-
work
Analog
10 bits/sec.
Telim Analog
monitoring station
BOSCH
300 bits/sec.
Analog
monitoring station
Data transmis-
sion to TAP/UCP
server
Euromessage
message (tone
dialing)
Euromessage
receiver
In the event of tampering or damage to the relaying
telephone line, the AT 2000 can send a message (tamper
release).
The absolute operating procedure on the telephone line is
enabled by the blockade release.
Monitoring of the auto dialer and the telephone network
occurs through a routine call.
The AT 2000 has a tamper contact.
Power monitoring: network, battery, undervoltage
The event storage for up to 31 events can be read out using
a PC.
AT 2000 AFS
In addition, the AT 2000 AFS can handle the remote-
control of outputs with the BOSCH transmission
procedure.
The four outputs (relays) can be controlled depending
on the message line status (locally) and via remote
control by reception and transmission equipment using
the Bosch procedure.
Certifications and Approvals
Region Certification
Europe CE AT 2000 Analog/AFS
Germany VdS G 196808 AT 2000 Analog
Installation/Configuration Notes
Telephone line
The AT 2000 Analog enables connection to main and
auxiliary lines and is connected to the telephone line via
a TAE junction box.
Fire detection technology
Interface according to VDE 0833 part 2 can be provided
optionally.
Parts Included
Type Qty. Component
AT 2000 Analog
incl. housing and
power supply
1 Analog alarm transceiver
with housing and power supply
AT 2000 Analog
incl. housing
1 Analog alarm transceiver
with housing (without power supply)
AT 2000 Analog
Installation module
1 Analog alarm transceiver
Installation module (without housing and
power supply)
AT 2000 AFS
Installation module
1 Analog/remote-controlled alarm transceiver
Installation module (without housing and
power supply)
Technical Specifications
Housing versions and installation modules
Operating voltage 10.5 V to 14.5 V
Current consumption
Standby current
Approx. 60 mA
Transmission mode
Approx. 85 mA
Additional current per activated
relay
Approx. 12 mA
Trigger resistance 5.62 kilohm ±1%
Activation time > 200 ms
www.boschsecurity.com Bosch Security Systems B.V.