Bosch Appliances 8-Dec Home Security System User Manual


 
Detectors and Accessories | Motion PIR | 149
Australia C-tick
Ukraine IEC 60839‑1‑3‑2001,
IEC 60839‑2‑2‑2001,
IEC 60839‑2‑6‑2001, GOST 26342‑84,
GOST 27990‑88
Europe Complies with EN50131-2-2 Grade 2
Installation/Configuration Notes
Coverage Patterns
Top View Broad: 11 m x 11 m (35 ft x 35 ft)
1 PIR pattern 1 2 PIR pattern 2
Side View Broad: 11 m x 11 m (35 ft x 35 ft)
1 PIR coverage patterns (1 and 2) 2 Look-down zone
Mounting
The recommended mounting height is 2.3 m to 2.7 m
(7.5 ft to 9 ft).
The detector can be mounted:
On a flat wall (surface, semi-flush), with the optional
B335 Swivel-mount Bracket, or with the optional B328
Gimbal-mount Bracket.
In a corner (the junction of two perpendicular walls).
On the ceiling with the optional B338 Ceiling-mount
Bracket.
Note The use of optional mounting brackets can
reduce the detector's range and increase the
dead zone areas.
Power Considerations
Power Limits
Input power must be provided by an approved limited
power source. All outputs must be connected to SELV
(safety extra-low voltage) circuits only.
Standby Power
This detector has no internal standby battery. For UL Listed
product installations, 4 hr (40 mAh) of standby power must
be supplied by the control unit or by a UL Listed burglary
power supply.
Parts Included
Quant. Component
1 Detector
1 Hardware pack
1 Literature pack
Technical Specifications
Environmental Considerations
Complies with EN50131-2-2 Environmental Class II, Security Grade 2
Relative Humidity: 0 to 85%, non-condensing
Temperature (operating): -29°C to +49°C (-20°F to +120°F)
For UL Listed product installations, 0°C to
+49°C (+32°F to +120°F)
Mechanical Properties
Color: white
Dimensions: 13.2 cm x 6.1 cm x 4.8 cm (5.2 in. x 2.4 in. x 1.9 in.)
Material: High-impact ABS plastic
Radio Frequency
Interference (RFI)
Immunity
No alarm or setup on critical frequencies in the range
from 26 MHz to 2 GHz at field strengths less than
30 V/m.
Outputs
Digital Alarm: 5 V normally, grounded for 4 sec during alarm.
Relay: Solid state, supervised, Form A normally-closed (NC) con-
tacts rated for 125 mA, 28 VDC, 3 W.
Tamper: Normally-closed (NC) contacts (with cover on) rated at
28 VDC, 125 mA maximum.
Connect tamper circuit to 24-hour protection circuit.
Power Requirements
Current (alarm): 18 mA
Current (standby): 10 mA maximum at 12 VDC
Voltage (operating): 10 VDC to 14 VDC