Mitsubishi Electronics QD77MS16 Home Security System User Manual


  Open as PDF
of 1038
 
13 - 5
Chapter 13 Control Sub Functions
(2) OPR retry operation when the workpiece is outside the range between the
upper and lower limits.
1) When the direction from the workpiece to the OP is the same as the "[Pr.44] OPR direction", a
normal machine OPR is carried out.
Pr. 44 OPR direction
Hardware upper limit switch
Hardware lower limit switch
Movement range
Machine OPR start
OP
Zero signal
Near-point dog
2) When the direction from the workpiece to the OP is the opposite direction from the "[Pr.44] OPR
direction", the operation carries out a deceleration stop when the near-point dog turns OFF, and
then carries out a machine OPR in the direction set in "[Pr.44] OPR direction".
Pr. 44 OPR direction
Near-point dog
Hardware upper limit switch
Hardware lower limit switch
Movement range
Machine OPR start
OP
Zero signal
In the above example 1) and 2), "0: Positive direction" is set in "[Pr.44] OPR direction"
REMARK
When the "0: Positive direction" is selected in "[Pr.44] OPR direction", the upper limit switch is set
to the limit switch in the OPR direction.
When the "1: Negative direction" is selected in "[Pr.44] OPR direction", the lower limit switch is
set to the limit switch in the OPR direction.
If inverting the install positions of upper/lower limit switches, hardware stroke limit function cannot
be operated properly.
If any problem is found for OPR operation, review "Rotation direction selection/travel direction
selection (PA14)" and the wiring for the upper/lower limit switch.
Fig. 13.2 OPR retry operation from on limit (limit signal OFF)