5 - 36
Chapter 5 Data Used for Positioning Control
[Pr.21] Current feed value during speed control
Specify whether you wish to enable or disable the update of "[Md.20] Current feed
value" while operations are performed under the speed control (including the
speed control in speed-position and position-speed switching control).
0: The update of the current feed value is disabled
The current feed value will not change.
(The value at the beginning of the speed control
will be kept.)
1: The update of the current feed value is enabled
The current feed value will be updated.
(The current feed value will change from the
initial.)
2: The current feed value is cleared to zero
The current feed value will be set initially to zero
and change from zero while the speed control is
in effect.
Note1: When the speed control is performed over two to four axes, the choice
between enabling and disabling the update of "[Md.20] Current feed value"
depends on how the reference axis is set.
Note2: Set "1" to exercise speed-position switching control (ABS mode).
[Pr.22] Input signal logic selection
Set the input signal logic that matches the signaling specification of the connected
external device, "[Cd.44] External input signal operation device" or external input
signal of servo amplifier (upper/lower limit switch, near-point dog).
Negative logic
(1) The current is not flowed through the input signal contact.
(a) FLS, RLS .............. Limit signal ON
(b) DOG, DI, STOP .... Invalid
(2) The current is flowed through the input signal contact.
(a) FLS, RLS .............. Limit signal OFF
(b) DOG, DI, STOP .... Valid
Positive logic
Opposite the concept of negative logic.
Note1: A mismatch in the signal logic will disable normal operation. Be careful of
this when you change from the default value.
Note2: Set the manual pulse generator input logic selection (b8) to axis 1. (Setting
of any of axes 2 to 4 is invalid.)
Note3: If the same external input signal is set to use to "[Pr.80] External input
signal selection" or "[Pr.95]
External command signal selection
" for the
multiple axes in the QD77MS16, the error "Input signal logic selection" of
those axes should be the same. Otherwise, "Input signal logic selection
setting error" (error code: 938) will occur when the PLC READY signal [Y0]
is turned ON, and the READY signal [X0] will not be turned ON.