11 - 14
Chapter 11 Manual Control
When the "JOG start signal" is turned ON again during deceleration caused
by the ON
OFF of the "JOG start signal"
When the "JOG start signal" is turned ON again during deceleration caused by the
ON
OFF of the "JOG start signal", the JOG operation will be carried out from
the time the "JOG start signal" is turned ON.
[QD77MS4 operation example]
OFF
ON
t
BUSY signal
[XC, XD, XE, XF]
OFF
ON
Forward run JOG operation
Forward run JOG start
si
g
nal [Y8, YA, YC, YE]
(Note): Refer to Section 3.3 for input/output signal of QD77MS16.
Fig. 11.9 Operation when the JOG start signal is turned ON during deceleration
When the "JOG start signal" is turned ON while the test function of
GX Works2 is used
When the "JOG start signal" is turned ON while the test function of GX Works2 is
used, it will be ignored and the JOG operation will not be carried out.
[QD77MS4 operation example]
In test mode flag
ON
t
Forward run JOG start signal
[Y8, YA, YC, YE]
OFF
ON
OFF
Forward run JOG
operation execution
JOG operation not possible
because this is not the
rising edge of the JOG
start signal
JOG operation not
possible because
the test function is
being used
(Note): Refer to Section 3.3 for input/output signal of QD77MS16.
Fig. 11.10 Operation when the JOG start signal is turned ON while the test function is used