Mitsubishi Electronics QD77MS16 Home Security System User Manual


  Open as PDF
of 1038
 
6 - 53
Chapter 6 Sequence Program Used for Positioning Control
6.5 Program details
6.5.1 Initialization program
[1] OPR request OFF program
This program forcibly turns OFF the "OPR request flag" ([Md.31] Status: b3)
which is ON.
When using a system that does not require OPR, assemble the program to
cancel the "OPR request" made by the Simple Motion module when the power is
turned ON, etc.
Data requiring setting
Set the following data to use the OPR request flag OFF request.
Setting item
Setting
value
Setting details
Buffer memory address
QD77MS2
QD77MS4
QD77MS16
[Cd.19]
OPR request flag OFF
request
1 Set to "1: Turn OPR request flag OFF". 1521+100n 4321+100n
n: Axis No.-1
:
Refer to Section 5.7 "List of control data" for details on the setting details.
Time chart for OPR OFF request
OFF
ON
OFF
0
1
0
ON
OFF
PLC READY signal [Y0]
READY signal
[X0]
OPR request OFF flag
( Md. 31 Status: b3)
Cd. 19 OPR request flag OFF request
Fig. 6.1 Time chart for OPR OFF request
[2] External command function valid setting program
This program is used to validate the "external command signal" beforehand when
using the external command functions (external start, speed change, speed-
position switching, position-speed switching, skip). Set which function to use
beforehand in "[Pr.42] External command function selection".
(Set the external command signal (DI) in "[Pr.95] External command signal
selection" at QD77MS16 use.)
Set the following data to validate the "external command signal".
Setting item
Setting
value
Setting details
Buffer memory address
QD77MS2
QD77MS4
QD77MS16
[Cd.8] External command valid 1 Set to "1: Validate external command". 1505+100n 4305+100n
n: Axis No.-1
:
Refer to Section 5.7 "List of control data" for details on the setting details.