Chapter 13 Control Sub Functions
13.4.5 Forced stop function
DANGER
When the forced stop is required to be wired, ensure to wire it in the negative logic using b-
contact.
Provided safety circuit outside the Simple Motion module so that the entire system will operate
safety even when the "[Pr.82] Forced stop valid/invalid selection" is set "1: Invalid". Be sure to
use the forced stop signal (EMI) of the servo amplifier.
By the Simple Motion module external input connection connector is connected forced
stop input, this function is available for all axes of servo amplifier. (The initial value is
"0: Valid".)
The forced stop input valid/invalid is selected by "[Pr.82] Forced stop valid/invalid
selection".
The details shown below explain about the "forced stop function".
[1] Control details
[2] Wiring the forced stop
[3] Setting the forced stop
[4] How to check the forced stop
[5] Precautions during control
[1] Control details
The servo warning "Controller forced stop warning" (warning No.: E7) will occur if
turned on the forced stop input signal when the "[Pr.82] Forced stop valid/invalid
selection" is set "0: Valid". And then it is available for all axes of servo amplifier.
The outline of the forced stop process is shown below.
Stop cause
Stop
axis
M code
ON
signal
after stop
Axis
operation
status
([Md.26])
after
stopping
Stop process
OPR control
Major
positioning
control
High-level
positioning
control
Manual control
Machine
OPR
control
Fast OPR
control
JOG/
Inching
operation
Manual
pulse
generator
operation
Forced stop
"Forced stop input
signal" OFF
All axes
No
change
Servo OFF
Servo OFF or free run (The operation stops with dynamic
brake)