5 - 9
Chapter 5 Data Used for Positioning Control
5.1.6 Setting items for positioning data
Positioning data must be set for carrying out any "major positioning control". The table
below lists the items to be set for producing the positioning data.
One to 600 positioning data items can be set for each axis.
For details of the major positioning controls, refer to Chapter 9 "Major Positioning
Control". For details of the individual setting items, refer to Section 5.3 "List of
positioning data".
Major positioning control
Positioning data
Position control
1 to 4 axis speed control
Speed-position switching
control
Position-speed switching
control
Other control
1-axis linear control
2/3/4-axis linear
interpolation control
1-axis fixed-feed control
2/3/4-axis fixed-feed
control
2-axis circular
interpolation control
NOP instruction
Current value changing
JUMP instruction
LOOP
LEND
[Da.1]
Operation
pattern
Independent
positioning
control
(Positioning
complete)
– –
Continuous
positioning
control
– –
Continuous path
control
– –
[Da.2]
Control system
Linear 1
Linear 2
Linear 3
Linear 4
Fixed-
feed 1
Fixed-
feed 2
Fixed-
feed 3
Fixed-
feed 4
Circular
sub
Circular
right
Circular
left
Forward
run speed 1
Reverse run
speed 1
Forward
run speed 2
Reverse run
speed 2
Forward
run speed 3
Reverse run
speed 3
Forward
run speed 4
Reverse run
speed 4
Forward
run
speed/
position
Reverse
run
speed/
position
Forward
run
position/
speed
Reverse
run
position/
speed
NOP
Current
value
changing
JUMP
instruction
LOOP LEND
[Da.3]
Acceleration time No.
– – –
[Da.4]
Deceleration time No.
– – –
[Da.5]
Axis to be interpolated
QD77MS2 QD77MS4
: 2 axes –: 1 axis, 3 axes, 4 axes
– – – – –
[Da.6]
Positioning address/
movement amount
New
address
– –
[Da.7]
Arc address
– – – –
– – –
[Da.8]
Command speed
– – –
[Da.9]
Dwell time/JUMP destination
positioning data No.
JUMP
destination
positioning
data No.
– –
[Da.10]
M code/Condition data
No./Number of LOOP to
LEND repetitions
JUMP
condition
data No.
Number of
LOOP to
LEND
repetitions
: Always set
: Set as required ("–" when not required)
: Setting not possible (If set, the error "Continuous path control not possible" (error code: 516) will occur at start.)
: Setting not required
(The setting value is invalid. When the value is the default value or within the setting range, there is no problem.)
: Two control systems are available: the absolute (ABS) system and incremental (INC) system.