Omron V022-E3-1 Thermostat User Manual


 
Note

Section 3-2
4-2 Starting the NT600S
When the NT600S is started, it will enter the RUN mode if system settings and
screen data registration have been completed. If no screen data has been regis-
tered or the screen data are destroyed, the System Menu will be displayed.
Before turning ON the power, check the following DIP switch settings on the
NT600S.
SW2-3 “Switch to the System Menu enabled/disabled” is set to OFF (enabled).
SW2-1 “Screen data forced initialize Yes/No” is set to No (ineffective).
For the DIP switch settings of the unit, refer to the “DIP switch settings” (page 26).
4-2-1 Changing the System Settings etc.
Follow the procedure below to change the system settings or screen data con-
tents.
Procedure 1. Turn ON the power to the NT600S.
The NT600S will enter the RUN mode and the start-up screen will be dis-
played. The start-up screen varies according to registered screen data.
2. Press appropriate touch switches to display the System Menu, and change
system settings. For the method for calling the System Menu, refer to the “Op-
erations with the System Menu” (page 70).
If the NT600S has failed to start up normally; an error message is displayed or no
screen is displayed, memory needs to be initialized.
For the memory initializing procedure, refer to Section 3-4 Initializing memory
(page 72).