6-4-2 How to Control NT600S Functions
This section describes how to control the functions of the NT600S.
Restrictions on allocating words
The PT status control area (PC PT) can be allocated to the PC memory areas
listed in the following table.
Symbol CSeriesPCs Allocated CVM1/CV Series PCs Allocated
DM Data memory
Data memory
CH Internal/Special Relay
Internal/Special Relay
TIM Timer Timer
CNT Counter Counter
HR Holding Relay
--
AR Auxiliary Relay
Auxiliary Relay
LR Link Relay
--
:OK :NG
Since all the CVM1/CV-series special auxiliary relays are allocated to the system,
they cannot be used for applications not related to the system.
The range of each memory area differs according to the PC type. See “Appendix L
PC Memory Map” (page 291) for more details.
Procedure 1. Use the support tool to allocate the PT status control area (PC PT) to the PC
memory.
2. Create a PC program to write control data to the “PT status control bits” of the
PT status control area.
Control timing of PT status control bits
The PT status control area (PC PT) is not read when the NT600S starts up. It
is only read, and control is only executed, when the contents of the PT status
control area are changed after the NT600S has been started up.
Since control of the NT600S statuses is executed after thebits corresponding to
the PT status control bits have changed, to execute control again the corre-
sponding bits must be specified again.
Application This example is of the NT600S being used as a warning lamp by using PT status
control bits.
Support Tool Settings
Make the following setting using the support tool.
Allocated word for the PT status control area: 0100