Omron V022-E3-1 Thermostat User Manual


 
Reference
Caution
Reference

Section 5-1
As the number of the numeral table is written, the PT status numeral setting
strobe flag is simultaneously set ON (1). After this is notified to the PC, this flag
reverts to OFF (0). Checking the status of this flag will provide a simple method
of checking if a number has been input from the NT600S.
Note that this function is not available with the character-string memory table.
PT status (refer to page 197)
The NT600S operation status and other information are written with the ON or
OFF of the bits as shown below.
15 14 13 12 11 10 9 8 Bit
PT status notify bits
0000Word m+2
PT operation status (1 (ON): RUN / 0 (OFF): STOP)
Screen switching strobe
Numeral setting strobe flag
Battery (1 (ON): LOW / 0 (OFF): NORMAL)
The PT status control area (PC to PT) can be allocated to the following PC areas.
Symbol CSeriesPCs Allocated CVM1/CV Series PCs Allocated
DM Data Memory
Data Memory
CH Internal/Special Relay
Internal/Special Relay
TIM Timer Timer
CNT Counter Counter
HR Holding Relay
--
AR Auxiliary Relay
Auxiliary Relay
LR Link Relay
--
:OK :NG
Since the special auxiliary relays of the CVM1/CV series PCs are allocated to the
system, they cannot be used for purposes other than the system use.
Set so that there is no overlap between the PT status control area and PT status
notify area. Otherwise the system may operate unpredictably.
When NT link (1:N) is set, the PT status notify area must be set for each con-
nected PT.