Omron V022-E3-1 Thermostat User Manual


 
Reference
Reference
Reference

Section 5-1
6-1-4 Switching the Screen Display
The following describes the procedure used to switch the NT600S screen display
by controlling from the PC.
The display screen can be switched also by pressing a touch switch during the
operation after registering a screen number to the touch switch. For this function,
refer to the “Standalone Function” (page 141).
To switch the NT600S screen display by controlling from the PC, write a screen
number at the “screen switch setting” in the PT status control area.
NT600S PC
Designated screen
PT status control area
Screen switch setting
PT status control setting
Screen number
Copy memory
table setting
[Screen switch setting in the PT status control area]
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Bit
PT status notify bits
Word n
Screen number (4-digit BCD)
Screen switch setting
Screen number: 0000 (screen clear, no-display)
0001 to 01000
Since the special auxiliary relays of the CVM1/CV series PCs are allocated to the
system, they cannot be used for purposes other than the system use.
The range of respective area varies with the type of PC. Refer to Appendix L PC
Memory Map (page 291).
Procedure 1. Use the support tool to allocate the PT status control area (PC to PT) to the PC
memory.
2. Create a PC program to write the number of the displayed screen to the
“screen switch setting word” in the PT status control area.
Use a 4-digit BCD (binary-coded decimal) value to set a screen number.
If a screen has been switched by operating the PT status control area (PC to PT),
the contents of the “currently displayed screen word” in the PT status notify area
(PT to PC) also change.
Screen switching timing
The NT600S screen switches when the contents of the “screen switch setting”
have changed. To re-specify the number of the currently specified screen, first
write the value 0000 to clear the screen before writing the appropriate screen
number.