I/O Memory Appendix B
The following table shows when timer PVs and Completion Flags will be reset.
Note The present value of TIM, TIMH(015), and TMHH(540) timers programmed will be updated even when
jumped between JMP and JME instructions.
Counter Area
The 256 counter numbers (C0000 to C0255) are shared by the CNT and CNTR(012) instructions.
Counter Completion Flags and present values (PVs) for these instructions are accessed with the
counter numbers.
When a counter number is used in an operand that requires bit data, the counter number accesses the
Completion Flag of the counter. When a counter number is used in an operand that requires word data,
the counter number accesses the PV of the counter.
Note It is not recommended to use the same counter number in two counter instructions because the
counters will not operate correctly if they are counting simultaneously. If two or more counter instructions
use the same counter number, an error will be generated during the program check, but the counters will
operate as long as the instructions are not executed in the same cycle.
The following table shows when counter PVs and Completion Flags will be reset.
Counter Completion Flags can be force-set and force-reset.
Counter PVs cannot be force-set or force-reset, although the PVs can be refreshed indirectly by force-
setting/resetting the Completion Flag.
There are no restrictions in the order of using counter numbers or in the number of NC or NO conditions
that can be programmed. Counter PVs can be read as word data and used in programming.
Instruction Mode change
between
PROGRAM and
RUN/MONITOR
FQM1 startup Operation in jumps
(JMP-JME) or tasks on
standby
Operation in interlocks
(IL-ILC)
TIMER: TIM PV 0
Flag OFF
PV 0
Flag OFF
PVs refreshed in operat-
ing timers
PV SV
(Reset to SV.)
Flag OFF
HIGH-SPEED TIMER:
TIMH(015)
ONE-MS TIMER:
TMHH(540)
Instruction Reset Mode change
between
PROGRAM and
RUN/MONITOR
FQM1
startup
At reset input Operation in
interlocks (IL-
ILC)
COUNTER: CNT PV 0000
Flag OFF
Maintained Reset Reset Maintained
REVERSIBLE
COUNTER: CNTR(012)