Omron FQM1-CM001 Home Security System User Manual


 
265
Programming Appendix A
Using Subroutines That Pass Parameters
With these subroutines, parameters can be passed to the subroutine when it is called and then the results of
processing in the subroutine can be returned to the main program. This enables using one subroutine while
changing the I/O addresses that are used. One subroutine can thus be used in multiple locations with similar
logic in the program to reduce the number of program steps and make the program easier to understand.
When passing parameters to a subroutine, execution is possible either with or without using Subroutine Input
Condition Flags.
Execution without Subroutine Input Condition Flags
The MCRO(099) instruction is used to call subroutines without Subroutine Input Condition Flags.
The following process is performed when MCR0(099) is executed.
1. Five words starting with the first input parameter word are copied to A510 through A514 (macro area inputs).
2. The specified subroutine is executed through RET(093).
3. When the subroutine is completed, the contents of A515 through A519 (macro area outputs) are copied to
five words starting with the first output parameter word.
4. Program execution continues with the next instruction after MCRO(099).
The first input and output parameter words can be changed when executing MCRO(099) to use the same sub-
routine for different purposes at different locations in the program.
As shown by the above process, using the macro function has the following limitations.
The parameters being passed must be stored in 5 continuous words.
The specified I/O parameters must be passed so that they correctly correspond to the program in the sub-
routine.
Note (1) A510 through A514 (macro area inputs) and A515 through A519 (macro area outputs) can be used
as work bits if MCRO(099) is not used.
(2) The words specified for the input/output parameter words can be I/O words, Auxiliary Area words,
DM Area words, or words in other memory areas.
(3) The subroutines called by MCRO(099) must be written in the same way as a normal subroutine,
e.g., between SBN(092) and RET(093).
Execution with Subroutine Input Condition Flags
Overview
Subroutines called with JSB(982) are always executed regardless of the input condition to the instruction. The
status of the input condition, however, is stored in an Auxiliary Area bit so that the status can be used to control
program execution within the subroutine.
Subroutines called with JSB(982) are executed even if their input condition is OFF and even in program sec-
tions interlocked with IL(002). The status of the input condition is stored in the Subroutine Input Condition Flag
corresponding to the subroutine. Subroutine Input Condition Flags are from A000 to A015 and correspond to
the subroutine numbers. The Subroutine Input Condition Flag can be used within the subroutine to control pro-
gram execution.
For example, a subroutine could perform jogging when the input condition is ON and perform stop processing
or deceleration when the input condition is OFF, or a subroutine could execute a communications instruction
when the input condition turned ON and then continue to monitor communications until a response is received
after the input condition turns OFF.
MCRO(099)
Subroutine number
First input parameter word
First output parameter word