WEBVISION™
99 95-7769—01
Daylight
Savings
Use this option to configure the settings for daylight savings. The following describes each field:
Enable Daylight Savings: This option is enabled by default. Disable this option if the daylight savings feature
is not required to be followed by the thermostat. Deselecting this option will disable the Start Month, Stop
Month, Start Day and Stop Day fields.
Start Month: This field is available for configuration only if the Enable Daylight Savings option field is
selected. Its default value is April. Change this option according to the daylight savings settings in the country
where the thermostat is installed.
Start Day: This field is available for configuration only if the Enable Daylight Savings option field is selected.
Its default value is First Sunday. Change this option according to the daylight savings settings in the country
where the thermostat is installed.
End Month: This field is available for configuration only if the Enable Daylight Savings option is selected. Its
default value is October. Change this option according to the daylight savings settings in the country where the
thermostat is installed.
Start Day: This field is available for configuration only if the Enable Daylight Savings option is selected. Its
default value is Last Sunday. Change this option according to the daylight savings settings in the country
where the thermostat is installed.
Configuration
ID
When you click this button, the button label is replaced by a 16 character alphanumeric number/code with every
2 digits separated by a period. This code represents the configuration information that define the equipment that
is connected to the thermostat. This code can be entered through the thermostat keypad using the installer
configuration:
Press the Run and Copy buttons simultaneously and navigate to the code. You are presented with a number
identified by C1. Enter the first 2 digits of the configuration ID that the wizard has generated. Continue entering
2 digits each for C2 through C8. Save this code using the Run button.
The configuration in the thermostat is changed to that in the wizard. The thermostat installer set up allows the
user to enter the configuration through the keypad. When the Configuration ID button is pressed the wizard
derives the configuration string that user can enter into the thermostat through keypad. This way, the
configuration in thermostat is same as it is the wizard with respect to inputs, outputs, setpoints, loop tuning
parameters, energy management parameters, bypass time.
Outputs Use this section to configure outputs.
Heat/Cool
Stages
Use these fields to configure the number of heat stages and cool stages for the application that the subbase is
being used for.
Outputs Model
Equipment
Type
Default
Value Number of Stages Available for Configuration
Heat Stages T7350H1009 Standard Three Stage • None
• One Stage
• Two Stage
• Three Stage (Not available if configured for
4 stages of cooling)
T7350H1017 Standard Heat Enable • Heat Enable
• One Stage
• Two Stage (Used as auxiliary relay or
second stage of heat or cool relay. Not
available if used as second stage of cooling)
Aux Heat Stages T7350H1009 Heat Pump One Stage • None (No auxiliary heating)
• One Stage (of auxiliary heat)
• Two Stage (of auxiliary heat)
Cool Stages T7350H1009 Standard Three Stage • None
• One Stage
• Two Stage
• Three Stage
T7350H1017 Standard Cool Enable • Heat Enable
• One Stage
• Two Stage (Used as auxiliary relay or
second stage of heat or cool relay. Not
available if used as second stage of
heating)
Compressor Stages T7350H1009 Heat Pump Two Stage • None
• One Stage
• Two Stage
Table 70. T7350 General Configuration Fields (Continued)
Name Definition