Honeywell 95-7769-01 Thermostat User Manual


 
WEBVISION™
47 95-7769—01
The wall module configuration affects the Use Wall Module
(under the Zone Option page) and Over Ride Priority (under
the Miscellaneous Parameters page). The possible values
of Use Wall Module and Override Priority is given in Table 20:
Optional Digital
Inputs
You can configure digital inputs. The
W7750A can be configured with a
maximum of two digital inputs. The
W7750B, W7750B Enhanced, and the
W7750C, can be configured with all four
digital inputs. CoilfreezeStat is available
on W7750C only.
Configure one of the following as an
optional digital point:
OccSensor
OccTimeclock
ProofAirFlow
EconEnable
IaqOverride
SmokeMonitor
DirtyFilter
Shutdown
WindowOpen
MonitorSw
ScheduleMaster
Dehumidify
Unused DI
Table 19. CVAHU Inputs Fields. (Continued)
Name Definition
Optional Analog
Inputs
You can configure both resistive and
voltage type analog inputs. The W7750A,
has one resistive analog input that can
be configured. The W7750B, W7750B
Enhanced, and W7750C have two
resistive and two voltage inputs that can
be configured. The W7750C supports the
OutdoorTemp20KNTC sensor type.
Configure one of the following as a
Resistive optional analog point:
DschgTempPT3000
OutdoorTempPT3000
RtnTempPT3000
DschgTemp20KNTC
OutdoorTemp20KNTC
RtnTemp20KNTC
Unused RAI
Configure one of the following as a
Voltage/current optional analog point:
Rtn HumidityC7600C
RtnEnthalpy
OdHumidityC7600C
OdEnthalpy
FilterPress
SpaceCO2
MonitorSensor
Rtn HumidityH7621
Rtn HumidityC7600B
OdHumidityH7621
OdHumidityC7600B
Unused VAI
The RtnHumidityH7621/31 and
OdHumidityH7621/31 humidity sensors
for voltage inputs are supported by
CVAHUs of model type CVAHU C whose
versions are 2.01.103 and above.
The other humidity sensor models H7620
and H7630 work fine when CVAHU is
configured to use the existing C7600C
humidity sensors.
The DischTemp20KNTC sensor can be
used to report valid temperatures up to
180 °F. This is applicable CVAHU C
models whose versions are 2.01.103 and
above. This is applicable to CVAHU
Model A also whose version is 2.01.13
and above.
Table 19. CVAHU Inputs Fields. (Continued)
Name Definition