7. Choose the number of cooling stages (1-4) or the type
(PWM or Floating) from the Cooling list.
8. Select the type of economizer from the Economizer list.
a. If the heating, cooling, or economizer is configured
as PWM, the Period, Zero Scale, and Full Scale
settings must be configured.
b. If the heating, the cooling, or the economizer is
configured as Floating, the Motor speed settings
must be configured.
9. Configure the Optional points. Refer to Table 16 on
page 45 for possible values.
10. Click Commit to save the settings or Reset to revert to
the last saved settings.
11. Click Next to display the Input Configuration page.
CVAHU Controller Outputs
Table 16 lists the CVAHU Outputs for each controller model.
NOTE: The optional points Free1AO, Free2AO,
Free1AORev, Free2AORev are available in the
W7750C Model of CVAHU only. These enumerations
must be selected to use terminals 6,7 and 8 of
W7750C model. These outputs can be driven by
XL15A or XL15C, but since Free1 and Free2 are
digital in nature, XL15A and XL15C can only
command these points to ON or OFF. Hence, these
points can be driven only by digital outputs of Xl15A/
Xl15C loops.
CVAHU Outputs fields
Table 17 lists the CVAHU Outputs fields.
Table 16. CVAHU Outputs for each Model.
Output W7750A W7750B W7750C
Heating 1 to 4 stages 1 to 4 stages, HeatPWM or
HeatingFloating
1 to 4 stages, HeatPWM,
HeatPWMRev, HeatAO,
HeatAORev, or HeatingFloating.
Cooling 1 to 4 stages 1 to 4 stages, CoolPWM or
CoolingFloating
1 to 4 stages, CoolPWM,
CoolPWMRev, CoolAO,
CoolAORev, or CoolingFloating.
Economizer EconNone or EconFloating EconNone, EconPWM, or
EconFloating
EconNone, EconPWM,
EconPWMRev, EconAO,
EconAORev or EconFloating.
Optional Points OccStatus, AuxEcon, Free1, Free2,
Free1PulseOn, Free1PulseOff.
Maximum of one optional point.
OccStatus, AuxEcon, Free1, Free2,
Free1PulseOn, Free1PulseOff.
Maximum of three optional points.
OccStatus, AuxEcon, Free1,
Free1Rev, Free2, Free2Rev
Free1PulseOn, Free1PulseOff,
Free1AO, Free1AORev, Free2AO,
Free2AORev.
No optional points available.
Table 17. CVAHU Outputs Fields.
Name Definition
Controller Type Select one of the following model types:
W7750A
W7750B
W7750C
The wizard does not allow commissioning
if incorrect Model Type is selected
Power Frequency Select one of the following options:
50 Hz
60 Hz
Equipment Type Select one of the following options:
Conventional
HeatPump
Heating Refer to table above for selecting Heating
options:
If you select Floating, enter the Motor
Speed settings.
If you select PWM, enter the PWM
settings.
Cooling Refer to the table above for selecting
Cooling settings:
If you select Floating, enter the Motor
Speed settings.
If you select PWM, enter the PWM
settings.
Economizer Refer to the table above for selecting
Economizer options:
If you select Floating, enter the Motor
Speed settings.
If you select PWM, enter the PWM
settings.