Honeywell 95-7769-01 Thermostat User Manual


 
WEBVISION™
123 95-7769—01
Fan Feedback nvoFcuStatus fanFeedback NumericPoint
External Active nvoFcuStatus externalActive NumericPoint
Fan Stages Active nvoFcuStatus fanStagesActive EnumPoint
Output Position 0 nvoFcuStatus outputPosition0 NumericPoint
Output Position 1 nvoFcuStatus outputPosition1 NumericPoint
Reheat Active nvoFcuStatus reheatActive EnumPoint
Effective Setpoint nvoFcuStatus activeSetPt NumericPoint
Space Temperature nvoFcuStatus spaceTemp NumericPoint
Reset Bypass Time nvoFcuStatus restBypassTime NumericPoint
Unit Status Mode nvoUnitStatus mode EnumPoint
Primary Heat Output nvoUnitStatus heatOutputPrimary NumericPoint
Secondary Heat Output nvoUnitStatus heatOutputSecondary NumericPoint
Cool Output nvoUnitStatus coolOutput NumericPoint
Economizer Output nvoUnitStatus econOutput NumericPoint
Fan Output nvoUnitStatus fanOutput NumericPoint
In Alarm nvoUnitStatus inAlarm NumericPoint
Terminal Load nvoTerminalLoad levPercent NumericPoint
Manual Mode nviManualMode ManualMode EnumPoint
Table 78. FCU Points Details (Continued)
Point Name Network Variable Field Point Type
Table 79. FCU Application of Points
Point name Graphics Alarms Trends Commandable Internal Use Valid Values
Occupied Cool (Setpoint) X Units=ºC
Precision=2
Min=10.0
Max=35.0
Standby Cool (Setpoint) X Units=ºC
Precision=2
Min=10.0
Max=35.0
Unoccupied Cool (Setpoint) X Units=ºC
Precision=2
Min=10.0
Max=35.0
Occupied Heat (Setpoint) X Units=ºC
Precision=2
Min=10.0
Max=35.0
Standby Heat (Setpoint) X Units=ºC
Precision=2
Min=10.0
Max=35.0
Unoccupied Heat (Setpoint) X Units=ºC
Precision=2
Min=10.0
Max=35.0
Current State X Default
Occupied
Unoccupied
Bypass
Standby