Honeywell 95-7769-01 Thermostat User Manual


 
WEBVISION™
95-7769—01 144
Outside Air Quality X X X Units=ppm
Precision=0
Min=0.0
Max=65535.0
Override X X X Default
Occupied
Unoccupied
Bypass
Standby
Proof Of Air Flow X X X Default
Off
Low
Medium
High
On
Return Air Enthalpy X X X Units=mA
Precision=1
Min=-256.0
Max=256.0
Return Air Humidity X X X Units=%
Precision=1
Min=0.0
Max=127.5
Return Air Temperature X X X Units=ºF
Precision=1
Min=-256.0
Max=256.0
Scheduled Occupancy X X X Default
Occupied
Unoccupied
Bypass
Standby
Sensor Occupancy X X X Default
Occupied
Unoccupied
Bypass
Standby
Shutdown X X X False or True
Smoke Monitor X X X False or True
Space CO2 X X X Units=ppm
Precision=0
Min=0.0
Max=65535.0
Space Temperature X X X Units=ºF
Precision=1
Min=-256.0
Max=256.0
Effective Setpoint X X X Units=ºF
Precision=1
Min=-256.0
Max=256.0
Window Open X X X Closed or Open
Table 85. UV Application of Points. (Continued)
Point Name Graphics Alarms Trends Commandable Internal Use Valid Values