Honeywell 95-7769-01 Thermostat User Manual


 
WEBVISION™
95-7769—01 76
Procedure
1. Click the Input button on the left pane to open the Input
Configuration page.
2. Enter information into available fields (see Table 54 on
page 76).
3. Click Commit to save the settings or Reset to revert to
the last saved settings.
4. Click Next to display the Equipment Control
Configuration page or Back to display the Output
Configuration page.
UV Inputs fields
UV Equipment Control Options
Use Table 55 to configure the Unit Ventilator Equipment
Control cascade, fan, and smoke control options.
Purpose
Define Equipment Control parameters that the Excel 10
Controller uses to control the unitary equipment.
Mode
Configuration can be performed with the wizard Off-line or
On-line.
Table 54. Unit Ventilator Inputs.
Name Definition
Space Temp Select one of the following Space Temp
sensor type options:
Unused
TR21 or TR23 (wall module)
UseReturn Temp
UseDischarge Temp
Select Physical Sensor (Wall Module or LCD
Wall Module) or Network Sensor Signal.
NOTE: The LCD Wall Module is supported
by the devices whose version is
v1.00.10 or above.
Optional
Digital Points
User address(es) for four optional digital
input points.
DI1
DI2
DI3
DI4
Select one of the following options:
UnUnsedDi
OccSensor - (usually a motion detector)
IaqOverrideIn
SmokeMonitor
DirtyFilterIn
ShutDown - (shuts down, and disables
automatic temperature control)
WindowOpen
Monitor - (generic switch input to be sent
out over the LonWorks Bus network)
CoilFreezeStat
AqstatMakeTmpRise - (make on
Temperature Rise)
AqstatBreakTmpRise - (break on
Temperature Rise)
TimeClock
DripPanFull - (locks out cooling when
contacts are made)
EconEnable - (Economizer enabled
when contacts are made)
Optional
Analog Points
User address(es) for analog points. Two
resistive and two voltage sensors are
available.
Select one of the following resistive options:
UnUsedRai
OutDoorTempPt3000
DischargeTempPt3000
ReturnTempPt3000
MixedAirTempPt3000
FanSwitch
DischargeTemp20kntc
ReturnTemp20kntc
MixedAirTemp20kntc
Select one of the following voltage options:
UnusedVai
RtnHumidityC7600C
ReturnEnthalpy
OdHumC7600C
OutdoorEnthalpy
OutdoorCO
FilterStaticPressDiff
SpaceCO2
OutdoorCO2
MonitorSensor1
RtnHumC7600B
OdHumC7600B
RtnHumidityH76721/31
OdHumidityH76721/31
NOTES:
1. If you configured a floating or
PWM economizer (see “UV
Outputs” on page 75), you
MUST select a Discharge Air
sensor to enable automatic
damper control.
2. The RtnHumidityH7621/31 and
OdHumidityH7621/31 humidity
sensors for voltage inputs are
supported by UVs whose
versions are 1.01.10 and above.
3. The DischTemp20KNTC sensor
can be used to report valid
temperatures up to 180 °F. This
is applicable for UVs whose
versions are 1.01.10 and above.
Table 54. Unit Ventilator Inputs. (Continued)
Name Definition