LONSpec Changes
Complete the following steps for migrating the existing LCBS
sites to WebVision:
1. Ensure that LonSpec database which is used to
commission the site is ready. Open the LonSpec project.
Click Network > Edit on the menu bar. The Edit
Network dialog box appears.
Fig. 46. Edit Network dialog box.
2. Click Advanced Features. The Advanced Features
dialog box appears.
Fig. 47. Advanced Features dialog box.
3. Set the Domain index for non-zero length domain to
0 (LNS based systems). Click OK to save the
changes.
4. Modify the original LonSpec project so that it does not
contain unsupported devices. The following are
frequently used:
a. XL15A
b. XL15B
c. Command Display 1 and 2
d. T7300
e. RapidLink/SLTA/PCLTA used by LonSpec, LonSta-
tion and XL15A.
f. RF Gateway
g. CX-VFD
It is highly recommended not to have these devices
physically connected to the Lon Network as it could
result in partial upload of binding information into WebVi-
sion, or worse interfere with WebVision functionality.
5. Disconnect WebVision from the network and re-
commission all the devices using LonSpec.
NOTE: When re-commissioning, please use full commission
command, not quick commission.
6. After re-commissioning, disconnect LonSpec from the
network.
WebVision Configuration Steps
Start the migration process on a fresh WebVision without any
existing config file. There should not be any devices present in
WebVision
1. Configure WebVision as given in the Quick Start Guide
and connect it to Ethernet and LON network.
2. Logon to WebVision through internet browser.
3. Click System > Network Setup. In Channel Info, set
the Domain ID to the same domain ID configured in
LonSpec typically 2C (44 decimal). The ID must be
specified in Hex format.Click Save to save the changes.
Fig. 48. Channel Info - Domain ID and Domain Length
fields.
4. Click the Devices tab and go to Device List screen.
5. Click Discover. A dialog box appears. Select Channel
as Channel 1 and click Discover. A progress bar
appears indicating the discovery progress.
6. After the discovery is complete, all the discovered
devices are listed on the left side of the table. Review
the subnet/node ids of discovered devices to ensure
that there are no conflicts. WebVision will detect the
clash and on confirmation from the user, it would
change the subnet/node id of the device.
NOTE: Changing subnet/node id will break any bindings
going in and out of that device. It is suggested that
the user find the clash manually and rectify them
through LonSpec.
7. Select all the devices by clicking on each device (or
click the SelectAll box) and then click Add to add them
to WebVision database.
NOTE: The user should click on the device to select the
device in the discovered list to do further operation
on them. Although mouse scrolling across the
discovered devices records appear as selection,
they are actually not selected
8. Enter a name for each device that should appear in then
UI and click Done to complete the discovery process.
9. Select all the devices and click Upload to upload the
device configuration onto WebVision. A progress bar
appears indicating the progress of the Upload
operation. Once the upload is complete, the Synced On
option is enabled for each device.
10. Ensure that all the devices are in Auto mode in the
Mode Column. If any device is in Manual or any other
mode, select that device and click Set Mode to Auto.
11. Click the Device Bindings sub-tab next to Device List
subtab.