Honeywell 95-7769-01 Thermostat User Manual


 
WEBVISION™
95-7769—01 168
T7350 Thermostat (T7350)
Table 92 provides the T7350 points detail and Table 93 on
page 169 provides the T7350 application of points.
Table 92. T7350 Point Details.
Point Name Network Variable Field Point Type
Occupied Cool nciSetpoints occupiedCool NumericWritable
Standby Cool nciSetpoints standbyCool NumericWritable
Unoccupied Cool nciSetpoints unoccupiedCool NumericWritable
Occupied Heat nciSetpoints occupiedHeat NumericWritable
Standby Heat nciSetpoints standbyHeat NumericWritable
Unoccupied Heat nciSetpoints unoccupiedHeat NumericWritable
Current State nviOccSchedule currentState EnumWritable
Next State nviOccSchedule nextState EnumWritable
Time To Next State nviOccSchedule timeToNextState NumericWritable
DLC Shed nviDlcShed DlcShed EnumWritable
Cover Communication Failed nvoAlarmStatus coverCommFail EnumPoint
Invalid IO Configuration nvoAlarmStatus invalidIOConfig EnumPoint
Invalid SubBase Type nvoAlarmStatus invalidSubBaseType EnumPoint
Network Communication Failed nvoAlarmStatus networkCommFail EnumPoint
Sensor Failed nvoAlarmStatus sensorFail EnumPoint
Application Mode nviApplicMode hvacMode EnumWritable
Manual Mode nviRequest objectRequest EnumWritable
Manual Occupancy nviOccManCmd occupancy EnumWritable
Temporary Setpoint nviSetpoint tempP NumericWritable
Auxiliary Heat 1 nvoData2 noAuxHeat1 EnumPoint
Auxiliary Heat 2 nvoData2 noAuxHeat2 EnumPoint
Auxiliary Relay nvoData2 relayAux EnumPoint
Auxiliary Relay nvoData2 auxRelay EnumPoint
Bypass Time nvoData1 bypassTime NumericPoint
Cool Relay 1 nvoData2 relayCool1 EnumPoint
Cool Relay 2 nvoData2 relayCool2 EnumPoint
Cool Relay 3 nvoData2 relayCool3 EnumPoint
Cool Stages On nvoData1 coolStgsOn NumericPoint
DLC Shed nvoData2 dlcShed EnumPoint
Days Left Keypad Holiday nvoData1 daysLeftKeypadHoliday NumericPoint
Dehumidifier Active nvoData2 dehumidActive EnumPoint
Discharge Air Limit nvoData2 DALimit EnumPoint
Discharge Air Temperature nvoData1 dischTemp NumericPoint
Economizer Output nvoUnitStatus econOutput NumericPoint
Effective Mode nvoData1 effMode EnumPoint
Effective Occupancy nvoData1 effOccCurrentState EnumPoint
Effective Setpoint nvoData1 effSetPt NumericPoint
Fan nvoData1 fan EnumPoint
Fan Relay nvoData2 relayFan EnumPoint
Heat Relay 1 nvoData2 relayHeat1 EnumPoint
Heat Relay 3 nvoData2 relayHeat3 EnumPoint
Heat Stages On nvoData1 heatStgsOn NumericPoint