12. Click Upload to upload the LON binding information
onto WebVision. A progress bar appears indicating the
progress of the Upload operation.
NOTES
1. Ensure all the devices are in Auto mode. If you
see any device in Manual or any other mode,
select that device and click Set Mode to Auto to
change the mode.
2. Click Download in Devices > Device List or
Devices > Device Bindings to initiate the
process of writing configuration data that is
present in WebVision to devices. This operation
should be performed only if it is absolutely
necessary. If there is no requirement to change
the configuration in the devices this operation
must not be performed.
3. The migration procedure has been tested with
LonSpec version 05.01.00.00 and later. It is
recommended that users use at least this version
for migration.
4. After the auto-resolution of Node ID conflict, if the
configuration upload fails (especially for XL15C),
user should wait a minute and retry the operation.
5. WebVision does not support access through
PPPoE connection. PPPoE is the data link layer
protocol used for broadband internet connections.
If the user is using PPPoE, the user is advised to
purchase a WiFi router or equivalent that supports
PPPoE and connect WebVision to the Ethernet
side of the router. Follow the User Guide of the
router to have the desired setup
6. It is recommended that all the device
configurations and bindings are checked field by
field to ensure that the migration was successful
as expected. If any information is found missing,
the user can retry upload operation of
configuration/bindings as applicable. If that does
not solve the problem, user should manually fill in
the missing information. Any attempts to do
download without performing this operation may
break the control system in the site.
7. Points can be overridden through any means in
WebVision for a period of time. However, if
WebVision is powered off during that period and
re-started, WebVision will not restore the point i.e.
will not cancel the override even if the specified
override time has elapsed. In this case, a stale
value will be observed in WebVision. To cancel
the original override operation, the user should
override the point again for a minute and that
would restore the default value.
8. If XL15Cs use Math Functions that are type
Network Special, the configuration will get
uploaded properly into WebVision. However the
WebVision interface does not show Math
Functions of type Network Special in the user