Honeywell 95-7769-01 Thermostat User Manual


 
WEBVISION™
95-7769—01 172
Economizer Output X X X Units=%
Precision=1
Min=-163.8
Max=163.8
Effective Mode X X X Default
Off
Cool
Heat
Emergency Heat
Reheat
Manual
Factory Test
Effective Occupancy X X X Default
Occupied
Unoccupied
Bypass
Standby
Effective Setpoint X X X Units=ºC
Precision=1
Min=-273.2
Max=327.7
Fan X X X Default
False
True
Fan Relay X X X Off or On
Heat Relay 1 X X X Off or On
Heat Relay 3 X X X Off or On
Heat Stages On X X X Units=null
Precision=0
Min=0.0
Max=255.0
Holiday X X X False or True
Next State X X X Occupied
Unoccupied
Bypass
Standby
Occ Null
Occupancy Sensor X X X Unoccupied
Occupied
Outdoor Temperature X X X Units=ºC
Precision=1
Min=-273.2
Max=327.7
Percent Cool Command X X X Units=%
Precision=1
Min=-163.8
Max=163.8
Percent Heat Command X X X Units=%
Precision=1
Min=-163.8
Max=163.8
Relay Heat 2 X X X Off or On
Remote Setpoint Offset X X X Units=ºF
Precision=0
Min=-128.0
Max=127.0
Table 93. T7350 Application of Points. (Continued)
Point Name Graphics Alarms Trends Commandable Internal Use Valid Values