Honeywell 95-7769-01 Thermostat User Manual


 
WEBVISION™
95-7769—01 116
Unoccupied Cool (Setpoint) X Units=ºC
Precision=2
Min=10.0
Max=35.0
Occupied Heat (Setpoint) X Units=ºC
Precision=2
Min=10.0
Max=35.0
Standby Heat (Setpoint) X Units=ºC
Precision=2
Min=10.0
Max=35.0
Unoccupied Heat (Setpoint) X Units=ºC
Precision=2
Min=10.0
Max=35.0
Current State X Default
Occupied
Unoccupied
Bypass
Standby
Next State X Default
Occupied
Unoccupied
Bypass
Standby
Time To Next State X Units=min
Precision=0
Min=0.0
Max=65535.0
DLC Shed X dlNoDlcShed
dlMinDlcShed
Air Flow Loss X False
True
Coil Freeze State X False or True
Dirty Filter X False or True
Frost Protect Alarm X False or True
Indoor Air Quality Override X False or True
Input Nv Fail X False or True
Invalid Setpoint X False or True
Low Limit Economizer Close X False or True
Node Disabled X False or True
Sensor Failure X False or True
Table 77. CVAHU Application of Points. (Continued)
Point Name Graphics Alarms Trends Commandable Internal Use Valid Values