Keypad/Display Configuration fields
Configuring the Setpoints page
Use the Setpoints Configuration page to configure the
heating and cooling setpoints, energy management features,
dehumidification features, recovery setpoints and bypass
timer.
Mode
Configuration can be performed with the wizard Off-line or
On-line.
Procedure
1. Click the Setpoints button on the left pane to open the
Setpoints Configuration page.
2. Enter information into available fields.
3. Click Commit to save the settings or Reset to revert to
the last saved settings.
4. Click Next to display the Equipment Control
Configuration page or Back to display the Keypad/
Display Configuration page.
T7350 Heating and Cooling Setpoints
Use Table 72 to specify the heating and cooling setpoints.
Table 72 also provides the default value and valid range for
each setpoint.
Table 71. Keypad/Display Configuration Fields.
Name Definition
Keypad Lockout Use this option to configure the keypad
lockout enable/disable through special
keypad sequence on the thermostat.
Enable All: Selecting this option will allow
the user to access any keys on the
thermostat. No lockout will be imposed.
Enable Setpoints & Override: This option
will lockout all keys except Temporary
Occupied, Temporary Not Occupied,
increase and decrease and information
key.
Info Key Only: This option will lockout all
keys information key
Display Units Use this option to configure the display
units in the thermostat for temperature
fields.
Degrees F: Select this option to set the
display unit for temperature fields as
degrees Fahrenheit.
Degrees C: Select this option to set the
display unit for temperature fields as
degrees Centigrade.
Clock Display Use this to configure the display mode of
time in the thermostat.
12 Hour (AM/PM): Selecting this option will
display the thermostat time in 12 hour
format.
24 Hour: Selecting this option will display
the thermostat time in 24 hour format
System Switch Use this option to configure the system
operation of the thermostat.
OFF: When this option is selected, heat
and cool states are disabled.
AUTO: The thermostat is configured for
Automatic Changeover. When this option
is selected, heating and cooling stages are
enabled to maintain heating and cooling
setpoints.
Cool: When this option is selected, cooling
stage operates on call for cooling. Heating
stages are disabled.
Heat: When this option is selected, heating
stage operates on call for heating. Cooling
stages are disabled.
Emergency Heat: This option is available
only when the equipment type is selected
as Heat Pump. Auxiliary heat serves as
stage one. Compressor stages are locked
off.
Table 72. Heating and Cooling Setpoints.
Setpoint
Default
Value
Min. and
Max.
Ranges Description
Cool
Unoccupied
Stpt
85 °F
(29 °C)
45-99 °F
(7-37 °C)
Unoccupied cooling setpoint
Display resolution:
1°F/°C.
Unoccupied Cool >=
Occupied Cool >=
Occupied Heat +2 °F
(1 °C)
Unoccupied Cool >=
Standby Cool >= Standby
Heat +2 °F (1 °C)
Cool
Standby
Stpt
78 °F
(26 °C)
45-99 °F
(7-37 °C)
Standby cooling setpoint
Display resolution:
1°F/°C.
Unoccupied Cool >=
Standby Cool >= Standby
Heat +2 °F (1 °C)
Cool
Occupied
Stpt
75 °F
(24 °C)
45-99 °F
(7-37 °C)
Occupied cooling setpoint
Display resolution:
1°F/°C.
Unoccupied Cool >=
Occupied Cool >=
Occupied Heat +2 °F
(1 °C)
Max Occupied Cool >=
Occupied Cool >=
Occupied Heat +2 °F
(1 °C)
Heat
Occupied
Stpt
70 °F
(21 °C)
40-90 °F
(4-32 °C)
Occupied heating setpoint
Display resolution:
1°F/°C.
Unoccupied Heat <=
Occupied Heat <=
Occupied Cool -2 °F
(1 °C)
Min Occupied Heat <=
Occupied Heat <=
Occupied Cool -2 °F
(1 °C)