Excel 10 Remote Input/Output
Device (RIO)
Table 82 provides the RIO points detail and Table 83 on
page 136 provides the RIO application of points.
Table 82. RIO Point Details.
Point name Network Variable Field Point Type
Communication Failed nvoAlarmStatus CommFail EnumPoint
Node Disabled nvoAlarmStatus NodeDisable EnumPoint
Sensor Failed nvoAlarmStatus SensorFail EnumPoint
Manual Mode nviManualMode manMode EnumWritable
Analog In 1 nvorioIO ai1 NumericPoint
Analog In 2 nvorioIO ai2 NumericPoint
Analog In 3 nvorioIO ai3 NumericPoint
Analog In 4 nvorioIO ai4 NumericPoint
Analog In 5 nvorioIO ai5 NumericPoint
Analog In 6 nvorioIO ai6 NumericPoint
Digital In 1 nvorioIO di1 EnumPoint
Digital In 2 nvorioIO di2 EnumPoint
Digital In 3 nvorioIO di3 EnumPoint
Digital In 4 nvorioIO di4 EnumPoint
Digital Out 1 nvorioIO d01 EnumPoint
Digital Out 2 nvorioIO d02 EnumPoint
Digital Out 3 nvorioIO d03 EnumPoint
Digital Out 4 nvorioIO d04 EnumPoint
Digital Out 5 nvorioIO d05 EnumPoint
Digital Out 6 nvorioIO d06 EnumPoint
Digital Out 7 nvorioIO d07 EnumPoint
Digital Out 8 nvorioIO d08 EnumPoint
Mode nvorioIO mode EnumPoint
Table 83. RIO Application of Points.
Point Name Graphics Alarms Trends Commandable Internal Use Valid Values
Communication Failed X False or True
Node Disabled X False or True
Sensor Failed X False or True
Manual Mode X X X X Enable
Disable
Manual
Suppress Alarms
Unsuppress Alarms
Analog In 1 X X X Units=ºF
Precision=1
Min=-256.0
Max=256.0
Analog In 2 X X X Units=ºF
Precision=1
Min=-256.0
Max=256.0