Honeywell 95-7769-01 Thermostat User Manual


 
WEBVISION™
95-7769—01 146
Fan Status nvoData FanOn EnumPoint
Field No nvoData FieldNo EnumPoint
Flow Sensor nvoIO siFlowSensorS3 NumericPoint
Flow Uncorrected nvoIO siFlowUncorrectedS3 NumericPoint
Flow Volts nvoIO siFlowVoltsS12 NumericPoint
Free 1 On nvoData Free1On EnumPoint
Fresh Air Ratio nvoData siFreshAirRatio NumericPoint
Heat Cool Switch nvoData HeatCoolSwitch EnumPoint
Heat Cool Switch nvoIO HeatCoolSwitch EnumPoint
Heat Stages nvoData HeatStages NumericPoint
IO Test In nvoIO IOTestIn EnumPoint
IO Test Switch nvoIO IOTestSwitch EnumPoint
Low Flow Alarm nvoData LowFlowAlarm EnumPoint
Manual Occupancy nvoData NetManOcc EnumPoint
Mode nvoData Mode EnumPoint
Model nvoIO Model NumericPoint
Monitor Switch nvoData MonSwitch EnumPoint
Monitor Switch nvoIO MonSwitch EnumPoint
Occupancy Sensor nvoIO OccupancySensor EnumPoint
Override nvoData OverRide EnumPoint
Override IO nvoIO OverRide EnumPoint
Peripheral Heat On nvoData PeriphHeatOn EnumPoint
Peripheral Heat Position nvoData ubPeriphHeatPosS1 NumericPoint
Reheat Percentage nvoData ubReheatPosS1 NumericPoint
Scheduled Occupancy nvoData SchedOcc EnumPoint
Sensor Occupancy nvoData SenOcc EnumPoint
Space Temperature nvoData siSpaceTempS7 NumericPoint
Space Temperature IO nvoIO siSpaceTempS7 NumericPoint
Supply Temperature nvoData siSupplyTempS7 NumericPoint
Temperature Sensor 0 nvoIO siTempSensorS7N0 NumericPoint
Temperature Sensor 1 nvoIO siTempSensorS7N1 NumericPoint
Temperature Setpoint nvoData siTempControlPtS7 NumericPoint
Window Open nvoData WindowOpen EnumPoint
Window Open IO nvoIO WindowOpen EnumPoint
Table 86. VAV II Point Details. (Continued)
Point Name Network Variable Field Point Type
Table 87. VAV II Application of Points
Point Name Graphics Alarms Trends Commandable Internal Use Valid Values
Occupied Cool (Setpoint) X Units=ºC
Precision=2
Min=10.0
Max=35.0
Standby Cool (Setpoint) X Units=ºC
Precision=2
Min=10.0
Max=35.0