79 95-7769—01
UV Zone Options
Use Table 58 to configure the Unit Ventilator Zone Options to
set the heating and cooling setpoints.
Purpose
Enter all outputs, including optional outputs, to be controlled
by the Unit Ventilator Controller.
Mode
Configuration can be performed with the wizard Off-line or
On-line.
Procedure
1. Click the Zone Options button on the left pane to open
the Zone Options Configuration page.
2. Enter information into available fields.
3. Click Commit to save the settings or Reset to revert to
the last saved settings.
4. Click Next to display the Miscellaneous Parameters
Configuration page or Back to display the H/C Stage
Parameters Configuration page.
UV Zone Options fields
UV Miscellaneous Settings
Use Table 59 to configure the miscellaneous Unit Ventilator
application settings.
Purpose
Enter all outputs, including optional outputs, to be controlled
by the Unit Ventilator Controller.
Mode
Configuration can be performed with the wizard Off-line or
On-line.
Procedure
1. Click the Miscellaneous button on the left pane to open
the Miscellaneous Parameters Configuration page.
2. Enter information into available fields.
3. Click Commit to save the settings or Reset to revert to
the last saved settings.
4. Click Next to display the PID Configuration page or
Back to display the Zone Options Configuration
page.
UV Miscellaneous settings
Table 58. Unit Ventilator Zone Options.
Name Definition
Cooling Occupied
Setpoint
Enter Occupied cooling setpoint;
range: 50 to 95 °F (10 to 35 °C).
Cooling Standby
Setpoint
Enter Standby cooling setpoint;
range: 50 to 90 °F (10 to 32 °C).
Cooling
Unoccupied
Setpoint
Enter Unoccupied cooling setpoint;
range: 50 to 90 °F (10 to 32 °C).
Heating Occupied
Setpoint
Enter Occupied heating setpoint;
range: 50 to 90 °F (10 to 32 °C).
Heating Standby
Setpoint
Enter Standby heating setpoint;
range: 50 to 90 °F (10 to 32 °C).
Heating
Unoccupied
Setpoint
Enter Unoccupied heating setpoint;
range: 50 to 90 °F (10 to 32 °C).
Use Wall Module
Setpoint
Select usage of setpoint adjustment
potentiometer on a connected Wall
Module.
This field is active if you selected a
Sensor_Setpoint type in the Wall Module
field on the Input tab.
Min. Limit
Setpoint
Provides a lower limit on the allowed
settings of the Wall Module’s setpoint
knob.
Enabled if Use Wall Module Setpoint is
Yes. Values range from 55 to 85 °F when
the setpoint knob type is absolute and
range for relative setpoint knob type is –9
to 9 DDf.
Max. Limit
Setpoint
Provides an upper limit on the allowed
settings of the Wall Module’s setpoint
knob.
Enabled if Use Wall Module Setpoint is
Yes. Values range from 55 to 85 °F when
the setpoint knob type is absolute and
range for relative setpoint knob type is –9
to 9 DDf.
Table 59. Unit Ventilator Miscellaneous Settings.
Name Definition
DLC Setpoint
Bump
Upon receipt of a DLC_Shed signal over
the LonWorks-Bus network, the current
operating setpoint value is bumped up/
down (for cool/heat modes) by this
amount. Select a value from 0 through 10.
Override Type Specify the type of Bypass override
functions that are available from the Wall
Module's Override button. You can select
one of the following options:
None
Normal
ByPassOnly
NOTE: No Continuous Unoccupied
allowed from the Wall Module's
Override button.
Table 58. Unit Ventilator Zone Options. (Continued)