Honeywell 95-7769-01 Thermostat User Manual


 
WEBVISION™
95-7769—01 152
Vacon NX Frequency Converter
(NXVFD)
Table 88 provides the NXVFD points detail and Table 89 on
page 153 provides the NXVFD application of points.
Table 88. NXVFD Point Details.
Point Name Network Variable Field Name Point Type
Application Type nciApplVer applicationType NumericWritable
Application Version nciApplVer versionNo NumericWritable
Application Ver Time nciApplVer time NumericWritable
Device Name nciDeviceName DeviceName String Writable
Adjust Input nviProcessIn3 levPercent NumericWritable
Free Analog Input nviProcessIn2 levPercent NumericWritable
Torque Reference nviProcessIn1 levPercent NumericWritable
Adjust Input / Actual Value 2 nviProcessIn3 levPercent NumericWritable
Clear Counter nviClrCntr value NumericWritable
Drive Speed Setpoint nviDrvSpeedStpt value NumericWritable
Free Analog / Input Actual Value 1 nviProcessIn2 levPercent NumericWritable
Reset Fault nviRstFault value NumericWritable
Torque Reference / Reference for PID nviProcessIn1 levPercent NumericWritable
AC Fault Code nvoProcessOut8 levPercent NumericPoint
Fault Active nvoDrvStatus bit3 BooleanPoint
DC Link Voltage nvoProcessOut7 levPercent NumericPoint
Drive Current nvoDrvCurnt amp NumericPoint
Drive Energy nvoDrvEnrgy elecKwh NumericPoint
Drive Power nvoDrvPwr powerKilo NumericPoint
Ready nvoDrvStatus bit0 BooleanPoint
Running nvoDrvStatus bit1 BooleanPoint
Drive Speed nvoDrvSpeed levPercent NumericPoint
Active Fault Code nvoActFault count NumericPoint
Motor Current nvoProcessOut3 levPercent NumericPoint
Motor Power nvoProcessOut5 levPercent NumericPoint
Motor Speed nvoProcessOut2 levPercent NumericPoint
Motor Torque nvoProcessOut4 levPercent NumericPoint
Motor Voltage nvoProcessOut6 levPercent NumericPoint
Output Frequency nvoProcessOut1 levPercent NumericPoint
Reference Eq Actual nvoDrvStatus bit5 BooleanPoint
Drive Run Hours nvoDrvRunHours timeHour NumericPoint
Counter Clockwise nvoDrvStatus bit2 BooleanPoint
Warning Active nvoDrvStatus bit4 BooleanPoint