Honeywell 95-7769-01 Thermostat User Manual


 
WEBVISION™
95-7769—01 148
Application Mode X X X X Default
Auto
Heat
Morning Warmup
Cool
Night Purge
Pre-cool
Off
Test
Emergency Heat
Fan Only
Free Cool
Ice
Maximum Heat
Economy
Dehumidify
Calibrate
Emergency Cool
Emergency Steam
Max Cool
HVAC Load
No Load
Manual Mode X X X X Enable
Disable
Manual
Suppress Alarms
Unsuppress Alarms
Manual Occupancy X X X X Default
Occupied
Unoccupied
Bypass
Standby
Temporary Setpoint X X X X Units=ºC
Precision=1
Min=10.0
Max=35.0
Auxiliary On X X X Off or On
Box Flow X X X Units=L/s
Precision=0
Min=0.0
Max=65535.0
Box Flow Control Setpoint X X X Units=L/s
Precision=0
Min=0.0
Max=65535.0
Box Heat Flow X X X Units=L/s
Precision=0
Min=0.0
Max=65535.0
Bypass Timer X X X Units=min
Precision=0
Min=0.0
Max=65535.0
DLC Shed X X X Restored or Shed
Damper Position X X X Units=%
Precision=1
Min=0.0
Max=100.0
Digital In 1 X X X False or True
Table 87. VAV II Application of Points (Continued)
Point Name Graphics Alarms Trends Commandable Internal Use Valid Values