Honeywell 95-7769-01 Thermostat User Manual


 
WEBVISION™
75 95-7769—01
UV Outputs
Use Table 53 to configure the Unit Ventilator Outputs for
heating and cooling stages. The outputs could be of stages,
PWM, or floating types. In addition, the number of fan speeds
and Economizer types must be set. You can also select
optional points.
Purpose
Select all outputs, including optional outputs, to be controlled
by the Unit Ventilator Controller.
Mode
Configuration can be performed with the wizard Off-line or
On-line.
Procedure
1. Click the UVOutputPane button on the left pane to
open the Output Configuration page.
2. Enter information into available fields.
3. Click Commit to save the settings or Reset to revert to
the last saved settings.
4. Click Next to open the Input Configuration page.
UV Outputs fields
UV Inputs
Use Table 54 to configure the Unit Ventilator Inputs for the
space temperature sensor type, wall module type, and the
voltage and digital inputs for a Unit Ventilator application.
Purpose
To select all sensors to be wired to the Unit Ventilator
Controller.
Mode
Configuration can be performed with the wizard Off-line or
On-line.
Table 53. Unit Ventilator Outputs.
Name Definition
Fan Speeds Select one of the following fan speeds:
No_Fan
One_Speed
Two_Speed
Three_Speed
Heating Select one of the following Heating types:
Heating_Stage_1
Heating_Stage_2
Heating_PWM
Heating_Floating
No_Heating
If you select Floating, the Motor Speed field
displays actuator speed in seconds.
If you select PWM, the PWM Settings
become editable.
Cooling Select one of the following Cooling types:
Cooling_Stage_1
Cooling_Stage_2
Cooling_PWM
Cooling_Floating
No_Cooling
If you select Floating, the Motor Speed field
displays actuator speed in seconds.
If you select PWM, the PWM Settings fields
become editable.
Economizer Selection of Economizer mixed air damper
actuator type: None (or packaged external
economizer), PWM, or Floating.
Econo_None_Pkgd
Econo_PWM
Econo_Floating
NOTE: If you configure a floating or PWM
economizer, you MUST select a
Discharge Air sensor (see Unit
Ventilator Inputs) to enable
automatic damper control.
Motor Speed Actuator motor speeds (in seconds).
Enabled with a selection of floating heating,
floating cooling or floating economizer.
Optional
Points
The first optional point is enabled if there is
sufficient room on the controller. After you
select the first point, the second one is
enabled if there is sufficient space, and so
on.
The following options are available:
Status_Occupied - (output energized
when controller is in Occupied mode)
AND/OR
Aux_Econ1 - (Emulates a T7300 – for
controlling an external economizer) AND/
OR
Free1 - (Network-controlled output) AND/
OR
Unused - (Point is unused)
Controller
Type
The Model type.
Power
Frequency
This field defines the line voltage that Excel
10 Controllers use and also tells LonSpec
the calculation required for noise immunity.
The calculation differs for 50 and 60 Hz
applications
PWM Settings PWM Period time (in seconds).
Zero Pulse time for a 0 percent output
signal (in seconds).
Full Pulse time for a 100percent output
signal (in seconds). This value must be
less than or equal to the PWM Period.
Table 53. Unit Ventilator Outputs. (Continued)
Name Definition