Honeywell 95-7769-01 Thermostat User Manual


 
WEBVISION™
173 95-7769—01
Scheduled State X X X Occupied
Unoccupied
Bypass
Standby
Occ Null
Space Humidity X X X Units=%
Precision=1
Min=-163.8
Max=163.8
Space Temperature X X X Units=ºC
Precision=1
Min=-273.2
Max=327.7
Stages Active X X X Units=null
Precision=0
Min=0.0
Max=7.0
SubBase Type X X X sbNul
sbSubasenone
sbSubase1
sbSubase2
sbSubase3
sbSubase4
sbSubase5
sbSubase6
sbSubase7
sbSubase8
sbSubase9
sbSubase10
sbSubase11
sbSubase12
sbSubase13
sbSubase14
sbSubase15
sbSubase16
System Mode X X X Default
Auto
Heat
Morning Warmup
Cool
Night Purge
Pre-cool
Off
Test
Emergency Heat
Fan Only
Free Cool
Ice
Maximum Heat
Economy
Dehumidify
Calibrate
Emergency Cool
Emergency Steam
Max Cool
HVAC Load
No Load
Temporary Setpoint X X X Units=ºF
Precision=1
Min=-8.0
Max=7.9
Table 93. T7350 Application of Points. (Continued)
Point Name Graphics Alarms Trends Commandable Internal Use Valid Values