Honeywell 95-7769-01 Thermostat User Manual


 
WEBVISION™
95-7769—01 140
Occupied Heat (Setpoint) X Units=ºC
Precision=2
Min=10.0
Max=35.0
Standby Heat (Setpoint) X Units=ºC
Precision=2
Min=10.0
Max=35.0
Unoccupied Heat (Setpoint) X Units=ºC
Precision=2
Min=10.0
Max=35.0
Current State X ocOccupied
ocUnoccupied
ocBypass
ocStandby
ocNul
Next State X ocOccupied
ocUnoccupied
ocBypass
ocStandby
ocNul
Time To Next State X Units=min
Precision=0
Min=0.0
Max=65535.0
DLC Shed X dlNoDlcShed
dlMinDlcShed
Air Flow Loss X false or true
Communication Failed X false or true
Dirty Filter X false or true
Drip Pan Full X false or true
Freeze State X false or true
Frost Protect X false or true
Indoor Air Quality Override X false or true
Invalid Setpoint X false or true
Low Limit Economizer Close X false or true
Node Disabled X false or true
Outside Air Quality X false or true
Sensor Failed X false or true
Table 85. UV Application of Points. (Continued)
Point Name Graphics Alarms Trends Commandable Internal Use Valid Values