Honeywell 95-7769-01 Thermostat User Manual


 
WEBVISION™
95-7769—01 158
Nvo L L Status _or Gate Status temp/LogicLoop_1/nvoLLStatus/data orGateStatus EnumPoint
Nvo L L Status _dc Ao Status temp/LogicLoop_1/nvoLLStatus/data dcAoStatus NumericPoint
Nvo Bypass _value temp/StartStopLoop_1/nvoBypass value NumericPoint
Nvo Bypass _state temp/StartStopLoop_1/nvoBypass state EnumPoint
Nvo St Stp Status _bypass Remaining temp/StartStopLoop_1/nvoStStpStatus/data bypassRemaining NumericPoint
Nvo St Stp Status _manual Mode temp/StartStopLoop_1/nvoStStpStatus/data/loopState manualMode EnumPoint
Nvo St Stp Status _effect Occupancy temp/StartStopLoop_1/nvoStStpStatus/data/loopState effectOccupancy EnumPoint
Nvo St Stp Status _sched Occupancy temp/StartStopLoop_1/nvoStStpStatus/data/loopState schedOccupancy EnumPoint
Nvo St Stp Status _sensor Occupancy temp/StartStopLoop_1/nvoStStpStatus/data/loopState sensorOccupancy EnumPoint
Nvo St Stp Status _sys Mode temp/StartStopLoop_1/nvoStStpStatus/data/loopState sysMode EnumPoint
Nvo St Stp Status _dlc Status temp/StartStopLoop_1/nvoStStpStatus/data/loopState dlcStatus BooleanPoint
Nvo St Stp Status _out Status temp/StartStopLoop_1/nvoStStpStatus/data outStatus EnumPoint
Nvo Bypass Arb _override Priority temp/StartStopLoop_1/nvoBypassArb/data overridePriority BooleanPoint
Nvo Bypass Arb _wall Mod Override temp/StartStopLoop_1/nvoBypassArb/data wallModOverride EnumPoint
Nvo Bypass Arb _bypass Timer temp/StartStopLoop_1/nvoBypassArb/data bypassTimer NumericPoint
Nvo Bypass Arb _occ Timer temp/StartStopLoop_1/nvoBypassArb/data occTimer NumericPoint
Nvo Bypass Arb _schedule X temp/StartStopLoop_1/nvoBypassArb/data scheduleX EnumPoint
Nvo Bypass Arb _occ Sensor temp/StartStopLoop_1/nvoBypassArb/data occSensor EnumPoint
Nvo Bypass Arb _man Override temp/StartStopLoop_1/nvoBypassArb/data manOverride EnumPoint
Nvo Bypass Arb _eff Occ State temp/StartStopLoop_1/nvoBypassArb/data effOccState EnumPoint
Nvo Bypass Arb _bypass State temp/StartStopLoop_1/nvoBypassArb/data bypassState NumericPoint
Table 90. XL15C Point Details. (Continued)
Point Name Network Variable Field Point Type
Table 91. XL15C Application of Points.
Point Name Graphics Alarms Trends Commandable Internal Use Valid Values
Current State X Occupied
Unoccupied
Bypass
Standby
Default
Next State X Occupied
Unoccupied
Bypass
Standby
Default
Time To Next State X Units=min
Precision=0
Min=0.0
Max=65535.0
Current State X Occupied
Unoccupied
Bypass
Standby
Default
Next State X Occupied
Unoccupied
Bypass
Standby
Default