Carrier 48/50AJ Air Conditioner User Manual


 
76
Table 92 — Remote Switch Logic Configuration
Monday In Period (
PER.X
DAYS
MON) — This vari-
able is used to include or remove Monday from the schedule.
Each period is assigned an occupied on and off time. If this
variable is set to YES, then Monday will be included in that peri-
od’s occupied time schedule. If this variable is set to NO, then
the period’s occupied time schedule will not be used on Monday.
This variable can be set for Periods 1 through 8.
Tuesday In Period (
PER.X
DAYS
TUE) — This variable
is used to include or remove Tuesday from the schedule. Each
period is assigned an occupied on and off time. If this variable
is set to YES, then Tuesday will be included in that period’s oc-
cupied time schedule. If this variable is set to NO, then the peri-
od’s occupied time schedule will not be used on Tuesday. This
variable can be set for Periods 1 through 8.
Wednesday In Period (
PER.X
DAYS
WED) — This
variable is used to include or remove Wednesday from the
schedule. Each period is assigned an occupied on and off time.
If this variable is set to YES, then Wednesday will be included
in that period’s occupied time schedule. If this variable is set to
NO, then the period’s occupied time schedule will not be used
on Wednesday. This variable can be set for Periods 1 through 8.
Thursday In Period (
PER.X
DAYS
THU) — This vari-
able is used to include or remove Thursday from the schedule.
Each period is assigned an occupied on and off time. If this
variable is set to YES, then Thursday will be included in that
period’s occupied time schedule. If this variable is set to NO,
then the period’s occupied time schedule will not be used on
Thursday. This variable can be set for Periods 1 through 8.
Friday In Period (
PER.X
DAYS
FRI) — This variable is
used to include or remove Friday from the schedule. Each peri-
od is assigned an occupied on and off time. If this variable is set
to YES, then Friday will be included in that period’s occupied
time schedule. If this variable is set to NO, then the period’s oc-
cupied time schedule will not be used on Friday. This variable
can be set for Periods 1 through 8.
Saturday In Period (
PER.X
DAYS
SAT) — This vari-
able is used to include or remove Saturday from the schedule.
Each period is assigned an occupied on and off time. If this
variable is set to YES, then Saturday will be included in that
period’s occupied time schedule. If this variable is set to NO,
then the period’s occupied time schedule will not be used on
Saturday. This variable can be set for Periods 1 through 8.
Sunday In Period (
PER.X
DAYS
SUN) — This variable
is used to include or remove Sunday from the schedule. Each
period is assigned an occupied on and off time. If this variable
is set to YES, then Sunday will be included in that period’s oc-
cupied time schedule. If this variable is set to NO, then the peri-
od’s occupied time schedule will not be used on Sunday. This
variable can be set for Periods 1 through 8.
Holiday In Period (
PER.X
DAYS
HOL) — This variable
is used to include or remove a Holiday from the schedule. Each
period is assigned an occupied on and off time. If this variable is
set to YES, then holidays will be included in that period’s occu-
pied time schedule. If this variable is set to NO, then the period’s
occupied time schedule will not be used on holidays. This vari-
able can be set for Periods 1 through 8.
Occupied From (
PER.X
OCC) — This variable is used to
configure the start time of the Occupied period. All days in the
same period set to YES will enter into Occupied mode at this
time.
Occupied To (
PER.X
UNC) — This variable is used to con-
figure the end time of the Occupied period. All days in the
same period set to YES will exit Occupied mode at this time.
Local Holiday Schedules (HOL.L) — This submenu
is used to program the local holiday schedules. Up to 30 holi-
days can be configured. When a holiday occurs, the unit will
follow the occupied schedules that have the HOLIDAY IN
PERIOD point set to YES.
Holiday Start Month (
HD.01 to HD.30

MON) — This is
the start month for the holiday. The numbers 1 to 12 corre-
spond to the months of the year (e.g., January = 1).
Holiday Start Day (
HD.01 to HD.30
DAY) — This is the
start day of the month for the holiday. The day can be set from
1 to 31.
Holiday Duration (
HD.01 to HD.30
LEN) — This is the
length in days of the holiday. The holiday can last up to 99
days.
Daylight Savings Time (DAY.S) — The daylight sav-
ings time function is used in applications where daylight
savings time occurs. The function will automatically correct
the clock on the days configured for daylight savings time.
DAYLIGHT SAVINGS START (DS.ST) — This submenu
configures the start date and time for daylight savings.
Daylight Savings Start Month (
DS.ST
ST.MN) — This is
the start month for daylight savings time. The numbers 1 to 12
correspond to the months of the year (e.g., January = 1).
Daylight Savings Start Week (
DS.ST
ST.WK) — This is
the start week of the month for daylight savings. The week can
be set from 1 to 5.
Daylight Savings Start Day (
DS.ST
ST.DY) — This is the
start day of the week for daylight savings. The day can be set
from 1 to 7 (Sunday=1, Monday=2, etc.).
Daylight Savings Minutes To Add (
DS.ST
MIN.A) — This
is the amount of time that will be added to the time clock for
daylight savings.
DAYLIGHT SAVINGS STOP (DS.SP) — This submenu con-
figures the end date and time for daylight savings.
Daylight Savings Stop Month (
DS.SP
SP.MN) — This is
the stop month for daylight savings time. The numbers 1 to 12
correspond to the months of the year (e.g., January = 1).
Daylight Savings Stop Week (
DS.SP
SP.WK) — This is
the stop week of the month for daylight savings. The week can
be set from 1 to 5.
Daylight Savings Stop Day (
DS.SP
SP.DY) — This is the
stop day of the week for daylight savings. The day can be set
from 1 to 7 (Sunday=1, Monday=2, etc.).
Daylight Savings Minutes To Subtract (
DS.SP
MIN.S)
This is the amount of time that will be removed from the time
clock after daylight savings ends.
REMOTE
SWITCH LOGIC
CONFIGURATION
(RMI.L)
SWITCH
STATUS
REMOTE INPUT STATE
(REMT)
REMOTE SWITCH CONFIGURATION (RM.CF)
0123
No Remote Switch Occ-Unocc Switch Start/Stop Override
OPEN
OPEN OFF xxxxx Unoccupied Start No Override
CLOSED ON xxxxx Occupied Stop Override
CLOSED
OPEN ON xxxxx Occupied Stop Override
CLOSED OFF xxxxx Unoccupied Start No Override