APPENDIX A — LOCAL DISPLAY TABLES (cont)
MODE — CONFIGURATION (cont)
ITEM EXPANSION RANGE UNITS CCN POINT DEFAULT PAGE NO.
BP BUILDING PRESS. CONFIG
BP.CF Building Press. Config 0-3 BLDG_CFG 0 29,64,65
BP.RT Bldg.Pres.PID Run Rate 5-120 sec BPIDRATE 10 64,65
BP.P Bldg. Press. Prop. Gain 0-5 BLDGP_PG 0.5 64,65
BP.I Bldg.Press.Integ.Gain 0-2 BLDGP_IG 0.5 64,65
BP.D Bldg.Press.Deriv.Gain 0-5 BLDGP_DG 0.3 64,65
BP.SO BP Setpoint Offset 0.0 - 0.5 “H2O BPSO 0.05 64,65
BP.MN BP VFD Minimum Speed 0-100 % BLDGPMIN 10 64,65
BP.MX BP VFD Maximum Speed 0-100 % BLDGPMAX 100 64,65
BP.FS VFD/Act. Fire Speed/Pos. 0-100 % BLDGPFSO 100 64,65
BP.MT Power Exhaust Motors 1-2 PWRM 1 64,65
BP.S Building Pressure Sensor Enable/Dsable BPSENS Dsable 64,65
BP.R Bldg Press (+/-) Range 0 - 1.00 “H2O BP_RANGE 0.25 64,65
BP.SP Building Pressure Setp. –0.25 -> 0.25 "H2O BPSP 0.05 29,64,65
BP.P1 Power Exhaust On Setp.1 0 - 100 % PES1 35 29,64,65
BP.P2 Power Exhaust On Setp.2 0 - 100 % PES2 75 29,64,65
B.CFG BP ALGORITHM CONFIGS 64,65
B.CFG
BP.SL Modulating PE Alg. Slct. 1-3 BPSELECT 1 64,65
B.CFG
BP.TM BP PID Evaluation Time 0 - 10 min BPPERIOD 1 64,65
B.CFG
BP.ZG BP Threshold Adjustment 0.1 - 10.0 “H2O BPZ_GAIN 1 64,65
B.CFG
BP.HP High BP Level 0 - 1.000 “H2O BPHPLVL 0.05 64,65
B.CFG
BP.LP Low BP Level 0 - 1.000 “H2O BPLPLVL 0.04 64-66
D.LV.T COOL/HEAT SETPT. OFFSETS
L.H.ON Dmd Level Lo Heat On –1 - 2 ^F DMDLHON 1.5 27,28,52
H.H.ON Dmd Level(+) Hi Heat On 0.5 - 20.0 ^F DMDHHON 0.5 27,28,52
L.H.OF Dmd Level(-) Lo Heat Off 0.5 - 2 ^F DMDLHOFF 1 27,28,52
L.C.ON Dmd Level Lo Cool On –1 - 2 ^F DMDLCON 1.5 27,28,52
H.C.ON Dmd Level(+) Hi Cool On 0.5 - 20.0 ^F DMDHCON 0.5 27,28,52
L.C.OF Dmd Level(-) Lo Cool Off 0.5 - 2 ^F DMDLCOFF 1 27,28,52
C.T.LV Cool Trend Demand Level 0.1 - 5 ^F CTRENDLV 0.1 52
H.T.LV Heat Trend Demand Level 0.1 - 5 ^F HTRENDLV 0.1 52
C.T.TM Cool Trend Time 30 - 600 sec CTRENDTM 120 52
H.T.TM Heat Trend Time 30 - 600 sec HTRENDTM 120 52
DMD.L DEMAND LIMIT CONFIG.
DM.L.S Demand Limit Select 0 - 3 (multi-text strings) DMD_CTRL 0 31,35,48,49,98
D.L.20 Demand Limit at 20 ma 0 - 100 % DMT20MA 100 31,49
SH.NM Loadshed Group Number 0 - 99 SHED_NUM 0 49
SH.DL Loadshed Demand Delta 0 - 60 % SHED_DEL 0 49
SH.TM Maximum Loadshed Time 0 - 120 min SHED_TIM 60 49
D.L.S1 Demand Limit Sw.1 Setpt. 0 - 100 % DLSWSP1 80 31,49
D.L.S2 Demand Limit Sw.2 Setpt. 0 - 100 % DLSWSP2 50 31,49
IAQ INDOOR AIR QUALITY CFG.
DCV.C DCV ECONOMIZER SETPOINTS
DCV.C
EC.MN Economizer Min.Position 0 - 100 % ECONOMIN 5 29,31,32,67-70
DCV.C
IAQ.M IAQ Demand Vent Min.Pos. 0 - 100 % IAQMINP 0 29,31,67-70
AQ.CF AIR QUALITY CONFIGS
AQ.CF
IQ.A.C IAQ Analog Sensor Config 0 - 4 (multi-text strings) IAQANCFG 0 32,67,69,70
AQ.CF
IQ.A.F IAQ 4-20 ma Fan Config 0 - 2 (multi-text strings) IAQANFAN 0 32,68-70
AQ.CF
IQ.I.C IAQ Discrete Input Config 0 - 2 (multi-text strings) IAQINCFG 0 31,35,67-70
AQ.CF
IQ.I.F IAQ Disc.In. Fan Config 0 - 2 (multi-text strings) IAQINFAN 0 32,68-70
AQ.CF
OQ.A.C OAQ 4-20ma Sensor Config 0 - 2 (multi-text strings) OAQANCFG 0 35,68-70
AQ.SP AIR QUALITY SETPOINTS
AQ.SP
IQ.O.P IAQ Econ Override Pos. 0 - 100 % IAQOVPOS 100 32,67,69,70,98
AQ.SP
DAQ.L Diff.Air Quality LoLimit 0 - 1000 DAQ_LOW 100 68-70
AQ.SP
DAQ.H Diff.Air Quality HiLimit 100 - 2000 DAQ_HIGH 700 32,68-70
AQ.SP
D.F.OF DAQ PPM Fan Off Setpoint 0 - 2000 DAQFNOFF 200 32,68-70
AQ.SP
D.F.ON DAQ PPM Fan On Setpoint 0 - 2000 DAQFNON 400 32,68-70
AQ.SP
IAQ.R Diff. AQ Responsiveness –5 - 5 IAQREACT 0 69,70
AQ.SP
OAQ.L OAQ Lockout Value 0 - 2000 OAQLOCK 0 69,70
AQ.SP
OAQ.U User Determined OAQ 0 - 5000 OAQ_USER 400 32,69,70
AQ.S.R AIR QUALITY SENSOR RANGE
AQ.S.R
IQ.R.L IAQ Low Reference 0 - 5000 IAQREFL 0 32,69,70
AQ.S.R
IQ.R.H IAQ High Reference 0 - 5000 IAQREFH 2000 32,69,70
AQ.S.R
OQ.R.L OAQ Low Reference 0 - 5000 OAQREFL 0 69,70
AQ.S.R
OQ.R.H OAQ High Reference 0 - 5000 OAQREFH 2000 69,70
IAQ.P IAQ PRE-OCCUPIED PURGE
IAQ.P
IQ.PG IAQ Purge Yes/No IAQPURGE No 69,70
IAQ.P
IQ.P.T IAQ Purge Duration 5-60 min IAQPTIME 15 69,70
IAQ.P
IQ.P.L IAQ Purge LoTemp Min Pos 0-100 % IAQPLTMP 10 69,70
IAQ.P
IQ.P.H IAQ Purge HiTemp Min Pos 0-100 % IAQPHTMP 35 69,70
IAQ.P
IQ.L.O IAQ Purge OAT Lockout 35-70 dF IAQPNTLO 50 69,70
DEHU DEHUMIDIFICATION CONFIG.
D.SEL Dehumidification Config 0-2 (multi-text strings) DHSELECT 0 69-71
D.SEN Dehumidification Sensor 1-2 (multi-text strings) DHSENSOR 1 69,70
D.EC.D Econ disable in DH mode? Yes/No DHECDISA Yes 69,70
D.V.CF Vent Reheat Setpt Select 0-1 (multi-text strings) DHVHTCFG 0 70,71
D.V.RA Vent Reheat RAT offset 0-8 ^F DHVRAOFF 0 70,71
D.V.HT Vent Reheat Setpoint 55-95 dF DHVHT_SP 70 70,71
D.C.SP Dehumidify Cool Setpoint 40-55 dF DHCOOLSP 45 70,71
D.RH.S Dehumidify RH Setpoint 10-90 % DHRELHSP 55 70,71