APPENDIX E — UPC OPEN CONTROLLER (cont)
NETWORK POINTS LIST
See legend on page 182.
BACNET
OBJECT ID
POINT NAME
READ
ONLY
UNITS
DEFAULT
VALUE
RANGE
BACNET
OBJECT NAME
UNIT
POINT
AV:9 Active Demand Limit W % n/a 0-100 dem_lim_1 DEM_LIM
AV:10 Air Temp Lvg Supply Fan R °F n/a n/a sat_1 SAT
AV:11 CEM AN1 4-20 ma J5,1-2 W mA n/a 0-20 cem4201_1 CEM4201
AV:12 CEM AN1 10K temp J5,1-2 W °F n/a -40-240 cem10k1_1 CEM10K1
AV:13 CEM AN2 4-20 ma J5,3-4 W mA n/a 0-20 cem4202_1 CEM4202
AV:14 CEM AN2 10K temp J5,3-4 W °F n/a -40-240 cem10k2_1 CEM10K2
AV:15 Temper Supply Air Setpt W °F n/a 0-100 sasptemp_1 SASPTEMP
AV:16 BP PID Evaluation Time Level W min 1 0-10 bpperiod_1 BPPERIOD
AV:17 BP Setpoint Offset W in H2O 0.05 0-0.5 bpso_1 BPSO
AV:18 BP Threshold Adjustment W n/a 1 0.1-10 bpz_gain_1 BPZ_GAIN
AV:22 Capacity Load Factor R % n/a n/a smz_1 SMZ
AV:23 Capacity Threshold Adj W n/a 1 0-10 z_gain_1 Z_GAIN
AV:24 Compressor A1 Run Hours R hr n/a n/a hr_a1_1 HR_A1
AV:25 Compressor A1 Starts R n/a n/a n/a cy_a1_1 CY_A1
AV:26 Compressor A1 Strikes R n/a n/a n/a cmpa1str_1 CMPA1STR
AV:27 Compressor A1 Timeguard R n/a n/a n/a cmpa1_tg_1 CMPA1_TG
AV:28 Compressor A2 Run Hours R hr n/a n/a hr_a2_1 HR_A2
AV:29 Compressor A2 Starts R n/a n/a n/a cy_a2_1 CY_A2
AV:30 Compressor A2 Strikes R n/a n/a n/a cmpa2str_1 CMPA2STR
AV:31 Compressor A2 Timeguard R n/a n/a n/a cmpa2_tg_1 CMPA2_TG
AV:32 Compressor B1 Run Hours R hr n/a n/a hr_b1_1 HR_B1
AV:33 Compressor B1 Starts R n/a n/a n/a cy_b1_1 CY_B1
AV:34 Compressor B1 Strikes R n/a n/a n/a cmpb1str_1 CMPB1STR
AV:35 Compressor B1 Timeguard R n/a n/a n/a cmpb1_tg_1 CMPB1_TG
AV:36 Compressor B2 Run Hours R hr n/a n/a hr_b2_1 HR_B2
AV:37 Compressor B2 Starts R n/a n/a n/a cy_b2_1 CY_B2
AV:38 Compressor B2 Strikes R n/a n/a n/a cmpb2str_1 CMPB2STR
AV:39 Compressor B2 Timeguard R n/a n/a n/a cmpb2_tg_1 CMPB2_TG
AV:40 Compressor Lockout Temp W °F 40 -20-55 oatlcomp_1 OATLCOMP
AV:41 Cool Trend Demand Level W °^F 0.1 0.1-5 ctrendlv_1 CTRENDLV
AV:42 Cool Trend Time (secs) W sec 120 30-600 ctrendtm_1 CTRENDTM
AV:43 Ctl.Temp RAT,SPT or ZONE R °F n/a n/a ctrltemp_1 CTRLTEMP
AV:44 Current Running Capacity R % n/a n/a htsg_cap_1 HTSG_CAP
AV:45 DAQ PPM Fan Off Setpoint W n/a 200 0-2000 daqfnoff_1 DAQFNOFF
AV:46 DAQ PPM Fan On Setpoint W n/a 400 0-2000 daqfnon_1 DAQFNON
AV:49 Dehumidify Cool Setpoint W °F 45 40-55 dhcoolsp_1 DHCOOLSP
AV:50 Dehumidify RH Setpoint W % 55 10-90 dhrelhsp_1 DHRELHSP
AV:52 Demand Limit Select W n/a 0 0-3 dmd_ctrl_1 DMD_CTRL
AV:53 Demand Limit Sw.1 Setpt. W % 80 0-100 dlswsp1_1 DLSWSP1
AV:54 Demand Limit Sw.2 Setpt. W % 50 0-100 dlswsp2_1 DLSWSP2
AV:56 Diff.Air Quality in PPM R n/a n/a n/a daq_1 DAQ
AV:58 Diff. AQ Responsiveness W n/a 0 -5-5 iaqreact_1 IAQREACT
AV:59 Dmd Level(-) Low Cool OFF W °^F 1 0.5-2 dmdlcoff_1 DMDLCOFF
AV:60 Dmd Level(-) Low Heat OFF W °^F 1 0.5-2 dmdlhoff_1 DMDLHOFF