Table 89 — Switch Logic Configuration
Table 90 — Display Configuration
Table 91 — Remote Switch Configuration
Remote Switch Logic Configuration
(Configuration
SW.LG
RMI.L) — The control allows for the configuration
of a normally open/closed status of the remote input switch via
RMI.L. If this variable is configured OPEN, then when the
switch is open, the remote input switch perceives the logic state
as OFF. Correspondingly, if RMI.L is set to CLOSED, the re-
mote input switch will perceive a closed switch as meaning
OFF. See Table 92.
Hot Gas Bypass — Hot gas bypass is an active part of
the A-Series ComfortLink™ capacity staging and minimum
evaporator load protection functions. It is controlled though the
Minimum Load Valve function.
The hot gas bypass option consists of a solenoid valve with
a fixed orifice sized to provide a nominal 3-ton evaporator load
bypass. A hot gas refrigerant line routes the bypassed hot gas
from Circuit A’s discharge line to Circuit A’s evaporator
distributor. When the unit control calls for hot gas bypass, the
hot gas enters the evaporator coil and adds refrigeration load
to the compressor circuit to reduce the cooling effect from
Circuit A.
The hot gas bypass system is a factory-installed option
installed on Circuit A only. This function is enabled at Config-
uration
COOL
MLV. When this function is enabled, an
additional stage of cooling capacity is provided by the unit
control staging sequences (see Tables 52, 54, 58, and 60).
Space Temperature Offset — Space temperature off-
set corresponds to a slider on a T56 sensor that allows the occu-
pant to adjust the space temperature by a configured range
during an occupied period. This sensor is only applicable to
units that are configured as either 2-Stage SPT or Multi-Stage
SPT control (Configuration
UNIT
C.TYP = 5 or 6).
Space Temperature Offset Sensor
(Configuration
UNIT
SENS
SP.O.S) — This configuration disables the reading
of the offset slider.
Space Temperature Offset Range
(Configuration
UNIT
SENS
SP.O.R) — This configuration establishes
the range, in degrees F, that the T56 slider can affect SPTO
when adjusting the slider from the far left (-SP.O.R) to the far
right (+SP.O.R). The default is 5° F.
Space Temperature Offset Value
(Temperatures
AIR.T
SPTO) — The Space Temperature Offset Value is the read-
ing of the slider potentiometer in the T56 that is resolved to
delta degrees based on SP.O.R.
TIME CLOCK CONFIGURATION
This section describes each Time Clock menu item. Not
every point will need to be configured for every unit. Refer to
the Controls Quick Start section for more information on what
set points need to be configured for different applications. The
Time Clock menu items are discussed in the same order that
they are displayed in the Time Clock table. The Time Clock
table is shown in Table 93.
Hour and Minute (HH.MM) — The hour and minute
of the time clock are displayed in 24-hour, military time. Time
can be adjusted manually by the user.
When connected to the CCN, the unit can be configured to
transmit time over the network or receive time from a network
device. All devices on the CCN should use the same time. Only
one device on the CCN should broadcast time or problems will
occur.
Month of Year (MNTH) — This variable is the current
month of the calendar year.
Day of Month (DOM) — This variable is the current
day (1 to 31) of the month.
Day of Week (DAY) — This variable is the current day
of the week (Monday = 1 through Sunday = 7).
Year (YEAR) — This variable is the current year (for ex-
ample, 2005).
Local Time Schedule (SCH.L) — This submenu is
used to program the time schedules. There are 8 periods
(PER.1 through PER.8). Each time period can be used to set
up a local schedule for the unit.
ITEM EXPANSION RANGE CCN POINT DEFAULT
SW.LG SWITCH LOGIC: NO / NC
FTS.L Filter Status Inpt-Clean Open/Close FLTSLOGC Open
IGC.L IGC Feedback - Off Open/Close GASFANLG Open
RMI.L RemSw Off-Unoc-Strt-NoOv Open/Close RMTINLOG Open
ECS.L Economizer Switch - No Open/Close ECOSWLOG Open
SFS.L Fan Status Sw. - Off Open/Close SFSLOGIC Open
DL1.L Dmd.Lmt.Sw.1 - Off Open/Close DMD_SW1L Open
DL2.L Dmd.Lmt.2 Dehumid - Off Open/Close DMD_SW2L Open
IAQ.L IAQ Disc.Input - Low Open/Close IAQINLOG Open
FSD.L Fire Shutdown - Off Open/Close FSDLOGIC Open
PRS.L Pressurization Sw. - Off Open/Close PRESLOGC Open
EVC.L Evacuation Sw. - Off Open/Close EVACLOGC Open
PRG.L Smoke Purge Sw. - Off Open/Close PURGLOGC Open
ITEM EXPANSION RANGE UNITS POINT DEFAULT
TEST Test Display LEDs ON/OFF TEST Off
METR Metric Display ON/OFF DISPUNIT Off
LANG Language Selection 0-1(multi-text strings) LANGUAGE 0
PAS.E Password Enable ENABLE/DISABLE PASS_EBL Enable
PASS Service Password 0000-9999 PASSWORD 1111
ITEM EXPANSION RANGE
CCN
POINT
REMT Remote Input State ON/OFF RMTIN
RM.CF Remote Switch Config 0 - 3 RMTINCFG
RMI.L RemSw
Off-Unoc-Strt-NoOv
Open/Close RMTINLOG
ITEM EXPANSION RANGE UNITS
CCN
POINT
SP.O.S Space Temp
Offset Sensor
Enable/
Disable
SPTOSENS
SP.O.R Space Temp
Offset Range
1 - 10 SPTO_RNG
SPTO Space Temperature
Offset
+- SP.O.R ^F SPTO