Carrier 48/50AJ Air Conditioner User Manual


 
150
APPENDIX B — CCN TABLES (cont)
STATUS DISPLAY TABLES (cont)
TABLE DISPLAY NAME RANGE UNITS POINT NAME WRITE STATUS
TEMPS
Air Temp Lvg Supply Fan dF SAT
Return Air Temperature dF RAT forcible
Outside Air Temperature dF OAT forcible
Space Temperature dF SPT forcible
Space Temperature Offset ^F SPTO forcible
Staged Gas LAT Sum dF LAT_SGAS
Staged Gas LAT 1 dF LAT1SGAS
Staged Gas LAT 2 dF LAT2SGAS
Staged Gas LAT 3 dF LAT23SGAS
Staged Gas Limit Sw.Temp dF LIMSWTMP
Cir A Sat.Condensing Tmp dF SCTA
Cir B Sat.Condensing Tmp dF SCTB
Cir A Sat.Suction Temp. dF SSTA
Cir B Sat.Suction Temp. dF SSTB
TSTAT
Control Mode………..: ascii text strings
Thermostat Y1 Input On/Off Y1 forcible
Thermostat Y2 Input On/Off Y2 forcible
Thermostat W1 Input On/Off W1 forcible
Thermostat W2 Input On/Off W2 forcible
Thermostat G Input On/Off G forcible
UINPUTS
Filter Status Input Dirty/Clean FLTS forcible
Fan request from IGC On/Off IGCFAN
Fire Shutdown Switch Alarm/Normal FSD forcible
Thermostat G Input On/Off G forcible
Thermostat W2 Input On/Off W2 forcible
Thermostat W1 Input On/Off W1 forcible
Thermostat Y2 Input On/Off Y2 forcible
Thermostat Y1 Input On/Off Y1 forcible
Economizer Control Input On/Off ECOSW forcible
Remote Economizer Enable Yes/No ECONENBL forcible
Econo Position Override Yes/No ECOORIDE forcible
Remote Input State On/Off RMTIN forcible
Supply Fan Status Switch On/Off SFS forcible
Demand Limit Switch 1 On/Off DMD_SW1 forcible
Demand Limit Switch 2 On/Off DMD_SW2 forcible
Pressurization Input Alarm/Normal PRES forcible
Evacuation Input Alarm/Normal EVAC forcible
Smoke Purge Input Alarm/Normal PURG forcible
IAQ - Discrete Input High/Low IAQIN forcible
Dehumidify Switch Input On/Off DHDISCIN forcible
UOUTPUTS
FANS
Supply Fan Relay On/Off SFAN_RLY
Supply Fan VFD Speed 0-100 % SFAN_VFD
Supply Fan Request Yes/No SFANFORC forcible
Power Exhaust Relay A On/Off PE_A
Power Exhaust Relay B On/Off PE_B
Power Exhaust Relay C On/Off PE_C
Condenser Fan A On/Off CONDFANA
Condenser Fan B On/Off CONDFANB
COOLING
Compressor A1 Relay On/Off CMPA1
Compressor A2 Relay On/Off CMPA2
Minimum Load Valve On/Off MLV
Compressor B1 Relay On/Off CMPB1
Compressor B2 Relay On/Off CMPB2
HEATING
Heat Relay 1 On/Off HS1
Heat Relay 2 On/Off HS2
Relay 3 W1 Gas Valve 2 On/Off HS3
Relay 4 W2 Gas Valve 2 On/Off HS4
Relay 5 W1 Gas Valve 3 On/Off HS5
Relay 6 W2 Gas Valve 3 On/Off HS6
Heat Interlock Relay On/Off HIR forcible
ECONOMIZER
Economizer Act.Curr.Pos. 0-100 % ECONOPOS
Economizer Act.Cmd.Pos. 0-100 % ECONOCMD forcible
Economizer Power Relay On/Off ECON_PWR forcible
GENERAL OUTPUTS
Remote Alarm/Aux Relay On/Off ALRM forcible