APPENDIX A — LOCAL DISPLAY TABLES (cont)
MODE — CONFIGURATION (cont)
ITEM EXPANSION RANGE UNITS CCN POINT DEFAULT PAGE NO.
CCN CCN CONFIGURATION
CCNA CCN Address 1 - 239 CCNADD 1 71,72
CCNB CCN Bus Number 0 - 239 CCNBUS 0 71,72
BAUD CCN Baud Rate 1 - 5 (multi-text strings) CCNBAUDD 3 71,72
BROD CCN BROADCST DEFINITIONS
BROD
TM.DT CCN Time/Date Broadcast ON/OFF CCNBC On 71,72
BROD
OAT.B CCN OAT Broadcast ON/OFF OATBC Off 71,72
BROD
ORH.B CCN OARH Broadcast ON/OFF OARHBC Off 71,72
BROD
OAQ.B CCN OAQ Broadcast ON/OFF OAQBC Off 71,72
BROD
G.S.B Global Schedule Broadcst ON/OFF GSBC Off 71,72
BROD
B.ACK CCN Broadcast Ack'er ON/OFF CCNBCACK Off 71,72
SC.OV CCN SCHEDULES-OVERRIDES
SC.OV
SCH.N Schedule Number 0 - 99 SCHEDNUM 1 27-29,71,72
SC.OV
HOL.T Accept Global Holidays? YES/NO HOLIDAYT No 72
SC.OV
O.T.L. Override Time Limit 0 - 4 HRS OTL 1 27,72
SC.OV
OV.EX Timed Override Hours 0 - 4 HRS OVR_EXT 0 72
SC.OV
SPT.O SPT Override Enabled ? YES/NO SPT_OVER Yes 27,72
SC.OV
T58.O T58 Override Enabled ? YES/NO T58_OVER Yes 27,72
SC.OV
GL.OV Global Sched. Override ? YES/NO GLBLOVER No 72
ALLM ALERT LIMIT CONFIG.
SP.L.O SPT lo alert limit/occ –10-245 dF SPLO 60 72,73,98
SP.H.O SPT hi alert limit/occ –10-245 dF SPHO 85 72,73,99
SP.L.U SPT lo alert limit/unocc –10-245 dF SPLU 45 72,73,98
SP.H.U SPT hi alert limit/unocc –10-245 dF SPHU 100 72,73,99
SA.L.O EDT lo alert limit/occ –40-245 dF SALO 40 43,72,73,99
SA.H.O EDT hi alert limit/occ –40-245 dF SAHO 100 72,73,99
SA.L.U EDT lo alert limit/unocc –40-245 dF SALU 40 72,73,99
SA.H.U EDT hi alert limit/unocc –40-245 dF SAHU 100 72,73,99
RA.L.O RAT lo alert limit/occ –40-245 dF RALO 60 72,73,99
RA.H.O RAT hi alert limit/occ –40-245 dF RAHO 90 72,73,99
RA.L.U RAT lo alert limit/unocc –40-245 dF RALU 40 72,73,99
RA.H.U RAT hi alert limit/unocc –40-245 dF RAHU 100 72,73,99
R.RH.L RARH low alert limit 0-100 % RRHL 0 72,73,99
R.RH.H RARH high alert limit 0-100 % RRHH 100 72,73,99
SP.L SP low alert limit 0-5 "H2O SPL 0 73,99
SP.H SP high alert limit 0-5 "H2O SPH 2 73,99
BP.L BP lo alert limit –0.25-0.25 "H2O BPL -0.25 73,99
BP.H BP high alert limit –0.25-0.25 "H2O BPH 0.25 73,99
IAQ.H IAQ high alert limit 0-5000 IAQH 1200 73,99
TRIM SENSOR TRIM CONFIG.
SAT.T Air Temp Lvg SF Trim –10 - 10 ^F SAT_TRIM 0 73
RAT.T RAT Trim –10 - 10 ^F RAT_TRIM 0 73
OAT.T OAT Trim –10 - 10 ^F OAT_TRIM 0 73
SPT.T SPT Trim –10 - 10 ^F SPT_TRIM 0 73
CTA.T Cir A Sat.Cond.Temp Trim –30 - 30 ^F SCTATRIM 0 73
CTB.T Cir B Sat.Cond.Temp Trim –30 - 30 ^F SCTBTRIM 0 73
SP.A.T Suct.Press.Circ.A Trim –50 - 50 PSIG SPA_TRIM 0 73
SP.B.T Suct.Press.Circ.B Trim –50 - 50 PSIG SPB_TRIM 0 73
DP.A.T Dis.Press.Circ.A Trim –50 - 50 PSIG DPA_TRIM 0 73,74
DP.B.T Dis.Press.Circ.B Trim –50 - 50 PSIG DPB_TRIM 0 73,74
SW.LG SWITCH LOGIC: NO / NC
FTS.L Filter Status Inpt-Clean Open/Close FLTSLOGC Open 74,75
IGC.L IGC Feedback - Off Open/Close GASFANLG Open 74,75
RMI.L RemSw Off-Unoc-Strt-NoOv Open/Close RMTINLOG Open 31,74,75
ECS.L Economizer Switch - No Open/Close ECOSWLOG Open 74,75
SFS.L Fan Status Sw. - Off Open/Close SFSLOGIC Open 74,75,100
DL1.L Dmd.Lmt.Sw.1 - Off Open/Close DMD_SW1L Open 31,74,75
DL2.L Dmd.Lmt.Sw.2 - Dehumid - Off Open/Close DMD_SW2L Open 31,74,75
IAQ.L IAQ Disc.Input - Low Open/Close IAQINLOG Open 31,32,74,75
FSD.L Fire Shutdown - Off Open/Close FSDLOGIC Open 74,75,99
PRS.L Pressurization Sw. - Off Open/Close PRESLOGC Open 74,75
EVC.L Evacuation Sw. - Off Open/Close EVACLOGC Open 74,75
PRG.L Smoke Purge Sw. - Off Open/Close PURGLOGC Open 74,75
DISP DISPLAY CONFIGURATION
TEST Test Display LEDs ON/OFF TEST Off 74,75
METR Metric Display ON/OFF DISPUNIT Off 74,75
LANG Language Selection 0-1(multi-text strings) LANGUAGE 0 74,75
PAS.E Password Enable ENABLE/DISABLE PASS_EBL Enable 74,75
PASS Service Password 0000-9999 PASSWORD 1111 74,75