Document No: LT0122 F3200 Installation & Programming Manual
Programming
Issue 2.7 5 July 2001 Page 6-33
Item Options Default
Bells Isol Key (V2.06 or earlier) Enable/Disable Enabled (V2.06 or earlier)
Ancil Isol Key (V2.06 or earlier) Enable/Disable Enabled (V2.06 or earlier)
Keys enable Enable/Disable
All keypad keys for:
Door open/Door closed Door open – all enabled
FF mode/non-FF mode Door closed – all disabled
Remote sounder silence options Enable/Disable sysflt reset, Sysflt reset – enabled
ffcif actions, all commands ffcif actions – enabled
Global network sounder silence Any KeyTX Enabled
Cmd TX Enabled
Receive Enabled
MAF board (NDU only) Present/not present
8 Zone Modules Number Fitted 0-8
8 Relay Modules Number Fitted 0-8
16 LED Display Number Fitted 0-4
Display LEDs Zones/Relays to LEDs 1-1 in order
Alarm Text 1 Smoke 1 Smoke
(Detector Type) 2 Heat
3 FSW (Flowswitch)
4 Manual
5 Valve
6 PSW (Pressure Switch)
7 SPKLR (Sprinkler)
8 & 9 Blank - All Programmable
Inst Alarm Text As per Alarm Text 4 Manual
AZC Mode 1 (Standard) 1 Std
2 (Hi Current)
3 (Lo Current)
4 (Tamper)
5 (Disabled)
TABLE 6.4.1
PROGRAMMABLE PARAMETERS
Continued .......