Tyco F3200 Smoke Alarm User Manual


 
Document No: LT0122 F3200 Installation & Programming Manual
Programming
Issue 2.7 5 July 2001 Page 6-31
GLOBAL DATA (CONTINUED)
The parameter “Fault sounder after 8 hrs isolate” enables the fault buzzer to be activated if
an isolate state (zone or relay) has been present for 8 hours with no operator intervention.
The AS4428.1 Standard requires this to be enabled.
New Zealand Mode
This option is available with V2.08 or later software and only for an NDU (not for F3200).
The programmable options that are specifically for New Zealand mode are described in
Chapter 12, and are as follows:
1. New Zealand mode enabled Y/N
2. Display bd Y/N
3. Batt vlow = alarm Y/N
4. Evac defect is fault Y/N
5. External defect is fault Y/N
When New Zealand mode is changed from disabled to enabled, a number of parameters are
set to New Zealand settings. When New Zealand mode is changed from enabled to
disabled, these parameters are set to Australian settings and are as follows:
PARAMETER AUSTRALIAN DEFAULT NEW ZEALAND DEFAULT
New Zealand mode enabled
Batt vlow is alarm
Evac defect is fault
External defect is fault
Zone alarm buzzer enabled
Zone fault buzzer enabled
System fault buzzer enabled
Fault sounder after 8 hours fault
Fault sounder after 8 hours isolate
Mains fail is fault after 8 hours
Battery low is fault
Battery connection test enabled
Hourly battery test enabled
Daily 40 minute battery test enabled
Charger high/low is fault
MCP maps to zone
N
N
N
N
Y
Y
Y
N
N
N
N
N
N
N
N
1
Y
N
Y
Y
Y
N
N
N
N
N
Y
Y
N
Y
N
None
The Australian default settings are to comply with AS1603.4. Compliance with AS4428.1
has different settings.