Tyco F3200 Smoke Alarm User Manual


 
F3200 Installation & Programming Manual Document No: LT0122
Configuring a FIP
Page 5-12 5 July 2001 Issue 2.7
5.5 ERROR MESSAGES DURING FIP CONFIGURATION
Listed below are some error messages that can appear on the LCD during installation.
Refer also to Section 6.6.3 System Faults in the Operator Manual LT0119.
Error messages that can occur on startup or exit from program mode
"Shift reg clocking fault"
"Invalid # shift regs.Total # regs=xxx # input regs=xxx"
These messages indicate a hardware fault with the shift register bus that connects the
Controller, MAF/PSU, 8 Zone, and 8 Relay modules. The fault could be on the Controller,
the interconnecting FRCs or any of the connected boards. Try connecting just the MAF/PSU
on its own and with different cables to isolate the problem.
"Shift reg driver fault"
This message indicates a problem with the software driver for the shift register bus.
"Clock crystal timebase check fail"
This message indicates a hardware fault on the Controller.
"Clock chip ram write read fail"
"Clock register write read fail"
"Clock startup fault"
These messages indicate a hardware fault on the Controller.
"Eprom CRC fail"
This message indicates the checksum of the software program code is incorrect. This can be
caused by a damaged EPROM or some other hardware fault on the Controller.
Error messages that can occur on entry to program mode
"This database is invalid and should be reinitialised-net dbase in non net panel"
This message is produced on entry to program mode when a database created with
networked F3200 or NDU software is used with non-networked software. This is unusable
and the database should be re-initialised and reprogrammed.